background image

Mydax, Inc. 

1M150W 

Water Cooled Chiller 

 

 

Designed for Lockheed Martin   

 SYSTEM 

OVERVIEW

 

 

System Fluid Schematic

 

 
 
REFRIGERATION 
 
Refer to drawing #D2914, the fluid (refrigerant & coolant) schematic.  The heart of this design is the refrigerant valves, 
shown at the left side of the drawing.  These are pulse-width-modulated valves, controlled directly by the system's 
embedded microprocessor.  By controlling the duration of the openings of the evaporator valve, a precisely determined 
flow of refrigerant is sent to the evaporator, allowing for exceptionally stable recirculating temperatures.  This system is 
designed to control the recirculating output temperature to ±0.5

°

C or better. 

 
The microprocessor sets the positions of the evaporator valve based upon the system heat load.  If the load increases, the 
evaporator valve is opened for longer durations, passing more refrigerant.  If the load decreases, the evaporator valve is 
opened for shorter durations, passing less refrigerant.  The microprocessor controls the bypass valve independently, 
shunting unneeded refrigerant through the bypass heat exchanger, where it is evaporated before it can reach the 
evaporator.  The superheat valve passes only enough refrigerant to maintain the proper gas temperature at the suction 
inlet of the compressor.  Using this technique, Mydax is able to run in load conditions of zero to full load and all 
combinations in between. 
 
During normal operation, the durations of the valve openings remain nearly constant.  Only major changes in heat load or 
system-wide power cycling cause large changes in the valve drives.  In the case of a step-wise change in heat load, the 
microprocessor quickly drives the valves to the new settings and refrigerant flow soon settles at the proper level. 
 
The controller sets the valve drives based primarily upon data received from RTD's (resistance temperature devices) 
located about the circuit.  The drawing shows RTD's at the discharge line leading from the recirculating pump, at the 
return line leading to the reservoir, between the condenser and receiver and at the compressor inlet.  The controller reads 
these and other sensors constantly and sets the refrigerant valves accordingly. 
 
Thus refrigerant flow is truly proportioned, allowing continuous compressor operation without the normal addition of 
pressure-actuated hot gas bypass valves.  All other refrigeration circuit components are used as in conventional systems.  
All permanent copper joints in the refrigeration circuit are brazed for extra strength.  Much of the circuitry is insulated to 
eliminate cooling capacity loss and unpredictable operation due to drafts or fluctuating ambient air conditions. 
 
 
RECIRCULATION 
 
This system is designed to recirculate deionized water. It is not designed to recirculate solutions of automotive antifreeze. 
Approximately 50 gallons are required to fill the 44 gallon polypropylene reservoir and associated plumbing.  The 
reservoir is fitted with two level sensors; one level sensor drives a FILL TANK alarm at the main panel, indicating 
coolant level has dropped somewhat.  The second sensor, the TANK EMPTY sensor, is connected to the safety interlock 
loop and shuts the system down if tripped. 
 
By using the data from the in-line turbine flow meter, the microprocessor will engage the Flow-OK relay at the selected 
GPM. The output of the relay is wired to a connector located on the rear panel of the unit, labeled "Flow OK",  which can 
be used to drive an external alarm. Further description of this is provided in the 

Installation 

chapter. 

 
The system is equipped with a deionizing filter; water flow through the filter is controlled by the microprocessor to 
maintain the water resistivity to between 300K and 500K ohms. The control algorithm will turn on the DI flow solenoid 
below 300K

 and turn it off above 500K

. Bypass flow through this filter is restricted to 0.5 GPM. 

 
 
 
 

Содержание 1M150W

Страница 1: ...vanced temperature control technology MYDAX INC INSTRUCTION OPERATION MANUAL 1M150W WATER COOLED CHILLER MYDAX INC 12260 Shale Ridge Road Auburn CA 95602 530 888 6662 FAX 530 888 0962 http www mydax c...

Страница 2: ...YSTEM OVERVIEW 4 INSTALLATION 6 FRONT PANEL CONTROLS 8 ALARM ERROR MESSAGES 10 DIAGNOSTIC DISPLAYS 11 SERVICE WARRANTY 14 SHIPPING STORAGE PROCEDURE 15 DRAWINGS PARTS LIST FRAME DRAWING FLUID DIAGRAM...

Страница 3: ...70 F 7 Gpm 40 F 20 PSI differential Electrical Service 460 480 VAC 60 Hz 3 phase 50 amp service Physical Parameters 65 H x 36 W x 58 D 1000 lbs dry weight STANDARD FEATURES This chiller is complete wi...

Страница 4: ...reas where potentially harmful conditions exist and in this manual to bring attention to such conditions This chiller uses materials that are subject to environmental regulations be sure to familiariz...

Страница 5: ...mpressor is hermetically sealed and no service should be required In the event that cleanup is necessary absorb oil with oil absorbent material and dispose of as a hazardous waste Follow approved clea...

Страница 6: ...TD s resistance temperature devices located about the circuit The drawing shows RTD s at the discharge line leading from the recirculating pump at the return line leading to the reservoir between the...

Страница 7: ...one power relay coil and a relay pole RL1 B The RESET switch serves to feed power to the relay which energizes the contactor When energized the contactor feeds power back to the relay so the RESET swi...

Страница 8: ...e starting to allow the crankcase heater to separate the refrigerant from the oil CONDENSER FLOW The condenser inlet and outlet fittings are 1 stainless steel female pipe thread fittings FPT Plumb the...

Страница 9: ...ow rate is visible on the front LCD display panel BYPASS VALVE To divert the recirculation flow from the output path back to the tank first open the Bypass valve then close the output flow adjustment...

Страница 10: ...ition is eliminated or the MUTE ALARM switch is depressed again Pressing MUTE ALARM when no alarm is active causes the alarm to sound once and the TEST ALARM display to appear SET Enables SET TEMPERAT...

Страница 11: ...decrements toggles tank temperature setpoint temperature and evaporator data view modes for multiple channel systems DECIMAL Display shows model number and software revision date and copyright RUN PU...

Страница 12: ...s too close to freezing 4 C The microprocessor shuts down the system with a fatal alarm Push Reset Indicates that a fatal alarm in the interlock circuit has occurred and the operator must push the Res...

Страница 13: ...a direct indicator of condenser temperature and pressure The microprocessor sends the CONDENSER HOT error message if the condenser temperature exceeds 54 C TEST PANEL 3 The first 3 sets of 4 digit nu...

Страница 14: ...e the Flow OK relay below the selected GPM The output of the relay is wired to a BNC connector labeled Flow OK located on the rear panel of the unit The shield and center pin are the normally open con...

Страница 15: ...setpoint temperatures of whichever recirculating channel was last selected at the Main Display and the system wide alarm history The second line indicates which recirculating channel was last selecte...

Страница 16: ...use of a torch In particular service of Mydax refrigeration circuits requires attention to the following 1 Use caution to protect components from heat damage 2 Prevent any moisture from entering the...

Страница 17: ...en run with water ethylene glycol should be added to the recirculating loop Verify that the concentration of ethylene glycol approaches 50 measure with a hydrometer in the recirculating loop before dr...

Отзывы: