Grounding straps should be installed on all loose conductive objects in the spraying area. This
includes material containers and equipment. Magnum Venus Products recommends grounding straps
be made of AWG No.18 stranded wire as a minimum and the larger wire be used where possible.
NFPA Bulletin No77 states that the electrical resistance of such a leakage path should be 1 meg ohm
(10
6
ohms) or less.
CAUTION
Whenever flammable or combustible liquids are transferred from one container to
another, or from one container to the equipment, both containers or container and
equipment shall be effectively bonded and grounded to dissipate static electricity.
For further information, see National Fire Protection Association (NFPA) 77, titled
“Recommended Practice on Static Electrical”. Refer especially to section 7-7
titled “Spray Application of Flammable and Combustible Materials”.
Introduction
This manual provides information for the operation, maintenance, and simple repair of the MVP
Innovator Plus System. The following procedures are included:
Installation, start-up, and shut-down instructions
Step-by-step operation instructions
Please read this manual carefully and retain for future reference. Follow the steps
in the order given, otherwise you may damage the equipment or injure yourself.
Component Assemblies
MVP’s Innovator Plus System consists of multiple components. Each component has its own
detailed manual and drawings. For complete repair and maintenance instructions, refer to the
appropriate manuals.
RECIRCULATION GUN
DISPENSE GUN
POWERHEAD
FLUID SECTION
CATALYST ALARM SENSOR
ULTRA PROPORTIONER
INNOVATOR PLUS CONTROL BOX
Air Requirements
1. The system requires a supply of air (30 cfm) and at least 100 psi (7 bar).
2. The unit requires a ½ inch (12 - 13 mm) inside diameter air hose minimum (use caution
when using quick disconnects; they may restrict air flow).
3. Preferably the air will be clean, dry, and oil free.