IGN 1
NO
C
NC
Relay
Contacts
FV(+)
GND
M2582 Fuel Valve
White
Black
Red
Ground
LCDT-PS-CD-N
*
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
FV(-)
*
+
–
IGN 1
F/V+
F/V-
GRD
MARK
IV
-N
terminal block
M2582 Fuel Valve
White
Black
Red
Ground
+
–
M2582 Fuel Valve
White
Black
Red
Ground
LCDT-PS-CD (R)-P
IGN 1
FV(-)
NO
C
NC
Relay
Contacts
FV(+)
GND
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
+
–
TYPICAL WIRING to SOLID-STATE TATTLETALE
®
Annunciators
M2582-C to LCDT-PS-CD (R)-P (positive ground)
M2582-C to LCDT-PS-CD-N (negative ground)
M2582-C to MARK
IV
-N (negative ground)
WARNING:
PERFORM THE WIRING OPERATION WITH THE POWER SOURCE “OFF” AND THE AREA MADE NON-
HAZARDOUS. MAKE SURE THE VOLTAGE AND CURRENT REQUIREMENTS ARE WITHIN THE FUEL SHUT-OFF VALVE RATINGS.
HARD CONDUIT WITH APPROVED SEALS IS REQUIRED BY THE NEC FOR HAZARDOUS AREA INSTALLATIONS.
M5081-C to LCDT-PS-CD (R)-P (positive ground)
FV(-)
*
GND
IGN 1
FV
NO
C
NC
Relay
Contacts
jumper
jumper
M5081 Terminal block
LCDT-PS-CD (R)-P
Terminal block
7
2
6
5
1
9
3
8
4
10
*
FV(-) FET output rated: 0.5 A @ 250 VDC max.
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
+
–
M5081-C to LCDT-PS-CD-N (negative ground)
FV(+)
GND
IGN 1
NO
C
NC
Relay
Contacts
jumper
jumper
M5081 Terminal block
LCDT-PS-CD-N
Terminal block
7
2
6
5
1
9
3
8
4
10
FV(-)
*
*
FV(-) FET output rated: 0.5 A @ 250 VDC max.
Relay contacts rated: 3 A, 30 VDC, 4 A, 125/250 VAC
+
–
M5081-C to MARK
IV
-N (negative ground)
IGN 1
F/V+
F/V-
GRD
MARK
IV
-N
terminal block
jumper
jumper
M5081 Terminal block
7
2
6
5
1
9
3
8
4
10
MARK
IV
has FET outputs rated: 0.5 A @ 250 VDC max.
*
*
Installation M-7980N page 9 of 12
1-800-548-1191 - http://www.partdeal.com - [email protected]