18
QM1190r7
Figure 13F
Variable Speed Operation
Electrical Wiring
Chapter 3
To Operate the Munters Drive variable with a 10-0V Signal, slide the ‘RUN’ switch, located on the circuit
board in the Munters Drive Box, to the ‘ON’ position. Connect wires from the ‘0-10V IN’ and ‘0-10V
COMMON’ terminals in the Munters Drive Box to the 10-0V output in the control.
See Figure 13F
.
10-0V
Output
In Control
Junction Box
(By Others)
Munters Drive Box
‘RUN’ Switch
Circuit Board in Munters Drive Box
Jumper
***WARNING***
The Blue Box electrical enclosure must not be
removed from mounting bracket. Removing
Blue Box from the mounting bracket will void the
warranty. Any water or other damage to the
controller will not be covered if the Blue Box is
removed.
***NOTE***
All Low Voltage wire must be shielded
cable. i.e. Belden 8770 or equivalent.