SCREEN
MultiGen GENERATOR MONITORING SYSTEM
MultiGen GENERATOR MONITORING SYSTEM
ACTION :
Press
COMMENTS :
This indicates that the
required custom pressure
sender has been
programmed.
4.5.4 Programming of custom temperature sender.
A custom sender is any sender that is not listed in
Appendix B. To complete this the user will need to have 5
points from a resistance curve of the sender that
correspond to temperature values.
These values can be obtained from the sender manufactuer
see example :-
Temperature °F
Resistance Ohms
100
950
125
480
150
110
175
80
200
32
45
Note the programming of the temperature points and
corresponding resistance values is an identical proceedure
to the pressure sender programming, a short explantion
follows.
Note all temperature values must be programmed in °F
values, regardless of whether the unit is required to display
°C or °F.
To convert from °C to °F. :- °C x1.8+32°F = °F
e.g. 50 °C x 1.8 + 32 °F = 122 °F
GENMOM.PM5
20/03/100, 10:30
45