84
9. MULTIGEN SPECIFICATIONS
INPUT
Rated Un
Direct connected voltages between 57.8
and 600 v. Standard voltages offered :-
63.5/110 V, 69.3 / 120 V, 120 / 208 V,
220/380 V, 230 / 400 V, 240 / 415 V,
277 / 480 V, for 3 ph 4 w
110 V, 120 V, 380 V, 400 V, 415 V, 440 V,
480 V, 600V for3 ph 3 w
Accuracy Range
20-120% Un
WorkingRange
5-125% Un
Burden
<0.5VA per phase
Overload
1.5 x Un continuous
4 x Un for 1 second
Rated In
1 or 5 amp
Accuracy Range
20-120% In
WorkingRange
5-125% In
Burden
<0.5VA per phase
Overload
4 x In continuous. 50 x In for 1 second
Frequency
50 / 60 Hz nominal range 45/65Hz
DC volts
10 to 30 volts
Hours Run
Updated every 2 minutes
SYSTEMS
Single phase
3 phase 3 wire unbalanced load
3 phase 4 wire unbalanced load
ACCURACY
Volt
0.5% of reading ± 2 digits
Amps
0.5% of reading ± 2 digits
Frequency
0.1Hz ± 1 digit
Coolant temp.
1% of reading ± 2 digits
Oil Pressure.
1% of reading ± 2 digits
Hours Run.
1% of reading ± 2 digits
DC volts
1% of reading ± 2 digits
GENMOM.PM5
20/03/100, 10:29
84