background image

24

Electrical Installation 

Field wiring must comply with all federal, state and local regulations. Circuit breakers, fuses, wiring and wire size must be installed per the National Electric 

Code (NEC). Voltage applied to Multistack chillers must be within plus/minus 10 percent of nameplate voltage. Voltage imbalance between phases may  

not exceed two percent. According to NEMA Standard MG-1-1998, a two percent voltage imbalance will cause a current imbalance of six to 10 times the 

voltage imbalance. Voltage imbalance between electrical phases must be kept to a minimum. Most Multistack chillers come with a single point of electrical 

connection (up to 500 amps) to simplify installation.  The main electrical conduit feeding the power junction box may enter from either the top, bottom, 

or left side of the panel when facing the panel. Chillers requiring more than 500 amps will have multiple electrical connection points (per the 500 amp 

requirement). 

 

Optional Single Module Field Connection

For single module installations, the power junction box can be deleted, but a power phase monitor must be installed.  The main electrical feed can connect 

directly to the module circuit breaker.   

Junction Box Support

Electrical Junction Box

Junction Box Support Leg

1. Attach the electrical junction box support. Line up the orange posts to ensure support is not backwards. The threaded plate slides in between frame.

2. The electrical junction box may be installed on either end of the chiller module.

3. Remove cover plate on appropriate end of the junction box, then bolt junction box to the support. 

4. Cut the junction box support leg to length and fasten to the bottom of box and then to the floor, if necessary.

5. Three-phase wire and the ground wire, sized according to the nameplate rating, should be run through the junction box. 

Buss bar Installation

NOTE

: Contact the local Multistack representative before installing the buss bar. Depending on the start-up representative’s policy, the attachment of 

the buss bar system, and power phase monitor to the electrician’s wire and lugs may be the responsibility of the electrician or the Multistack autho-

rized start-up technician. 

1.  Remove the buss duct covers.

2.  Remove the isolation switch cover

NOTE

: There is a dedicated chiller ground in this panel that must connect to a true earth ground. 

DANGER:

 To avoid the risk of electrical shock, personal injury or death, disconnect all electrical power to the unit before performing any mainte-

nance or service. The unit may have more than one electrical power supply. Assume all electrical wires are live, energized wires. Use lockout/tagouts. 

Содержание MS010XC

Страница 1: ...Modular Water Cooled Chillers Installation Operation Maintenance MS010XC MS015XC MS020XC MS030XC MS040XC MS050XC MS070XC MS085XC Standard and Total Access Modules...

Страница 2: ...t be followed This equipment must not be installed near an open flame per local codes and ASHRAE specifications Personnel servicing Multistack modular chillers must have at minimum a Class II EPA cert...

Страница 3: ...al codes DANGER Incorrect handling of HVAC equipment can result in explosions electrical shock or fire causing property damage injury and or fatality DANGER HVAC liquids and chemicals can be dangerous...

Страница 4: ...cu Ni E Double wall brazed V Other Model Number Nomenclature Unit Nameplate The chiller nameplate is located on the front of the control panel Use the unit model number nomenclature to identify speci...

Страница 5: ...stack sTotal Access option makes maintenance and serviceability even easier by placing heat exchangers at the outside of the module frame Manual isolation valves are factory installed Total Access uni...

Страница 6: ...compressors with separate refrigeration circuits Each refrigerant circuit has a high pressure HP and low pressure LP transducer that sends pressure signals to the module slave controller board Each co...

Страница 7: ...pipes on the condenser side During factory run testing the valves are adjusted to maintain 10 12 degrees superheat Check the superheat periodically to maintain this range Subcooling should normally be...

Страница 8: ...Storage gal 1 1 2 2 2 2 2 9 6 6 6 6 10 1 12 3 Circuit Configuration Dual Dual Dual Dual Dual Dual Dual Dual Quantity 1 1 1 1 1 1 1 1 Header System gal 7 7 7 7 7 7 7 14 Refrigerant Type R410A Charge lb...

Страница 9: ...check the overall condition of the equipment for damage such as broken copper lines oil leaks damaged controls and or electrical component housing or any major component torn loose from its mounting...

Страница 10: ...SensorWells 42 30 Mesh Filter Strainer May be shipped separately to sales office or job site Shipped inside 19 Junction Box 18 19 20 21 22 23 24 25 26 27 28 29 30 31 33 37 33 34 35 36 37 39 39 40 41...

Страница 11: ...mended clearances around the modular chiller There must be a minimum of six inches clearance over the top of the chiller including the top of master controller if installed on top of the module For sp...

Страница 12: ...of sample customer installation Enclosure panels are optional Module Dimensions No Panels Width A Depth B Height C Standard 28 47 5 8 64 Total Access MS010 050 32 56 67 Total Access MS070 34 56 67 Ext...

Страница 13: ...rs and Condensers Module Dimensions No Panels Width A Depth B Height C Standard 28 47 5 8 64 Total Access MS010 050 32 56 67 Total Access MS070 34 56 67 Extended Headers 28 62 1 8 64 Extended Headers...

Страница 14: ...aders on Condensers Module Dimensions No Panels Width A Depth B Height C Standard 28 47 5 8 64 Total Access MS010 050 32 56 67 Total Access MS070 34 56 67 Extended Headers 28 62 1 8 64 Extended Header...

Страница 15: ...Headers on Evaporators Module Dimensions No Panels Width A Depth B Height C Standard 28 47 5 8 64 Total Access MS010 050 32 56 67 Total Access MS070 34 56 67 Extended Headers 28 62 1 8 64 Extended Hea...

Страница 16: ...ns No Panels Width A Depth B Height C Standard 28 47 5 8 64 Total Access MS010 050 32 56 67 Total Access MS070 34 56 67 Extended Headers 28 62 1 8 64 Extended Headers 28 76 5 8 64 Standardized drawing...

Страница 17: ...installed across the pump to verify operation Multistack recommends a paddle type switch be installed in the leaving chilled water piping using a differential pressure switch Install it across the in...

Страница 18: ...all take no less than six hours or until the strainers are clean after flushing Old pipe systems with heavy encrustation shall be flushed a minimum of 24 hours and may require as much as 48 hours befo...

Страница 19: ...be at the same end or opposite ends depending upon jobsite requirements 2 Chiller modules are to be mounted on 4 x 4 x 4 inch steel rails or equivalent 21 inches center to center 3 Place 4 x 4 x 3 8 i...

Страница 20: ...Lubricate gaskets with solid vegetable shortening or other non petroleum based lubricant 10 Slide modules together lining up footing holes Install bottom joining bolts 11 Install top joining bolts 12...

Страница 21: ...er blank ends starting at bottom then move to the top blank that includes drain valves evaporator shown 16 Install filter stop rings on module closest to piping take off The 9 inch long pipe stubs sup...

Страница 22: ...shown MultistackTotal Access modular chillers are assembled into chiller arrays in the same manner as non Total Access modules as shown on Pgs 19 21 Grooved flange water connections onTotal Access ch...

Страница 23: ...ultiflush System Assembly The following procedure describes installation of the Multiflush automatic debris removal system This system is used periodically to remove dirt and debris from the from the...

Страница 24: ...al Junction Box Junction Box Support Leg 1 Attach the electrical junction box support Line up the orange posts to ensure support is not backwards The threaded plate slides in between frame 2 The elect...

Страница 25: ...ommends using Lines 1 and 3 7 Follow the procedure in Step 5 to complete installation of Lines 1 and 2 8 Follow the procedure in Step 5 to complete installation of Lines 1 and 2 9 With all three lines...

Страница 26: ...re performing any maintenance or service The unit may have more than one electrical power supply Assume all electrical wires are live energized wires Use lockout tagouts Module wiring connections to t...

Страница 27: ...to change product design literature and specifica tions without notice DANGER To avoid the risk of electrical shock personal injury or death disconnect all electrical power to the unit before perform...

Страница 28: ...LA1 RLA2 RLA3 2 Fuse Sizing Maximum Fuse MF Type RK5 Fuse MF 2 25 x RLA1 RLA2 RLA3 Where MF does not equal a standard size fuse the next larger size fuse should be used NOTES A RLA1 RLAofthelargestcom...

Страница 29: ...33 1 8 inch pieces on bottom Use T connectors in front middle The four corner connectors go on top front and rear 4 Install two long frames over spindle posts vertically in rear buss bar side Attach...

Страница 30: ...ris q q q Flow or differential pressure switch installed q q q ELECTRICAL Yes No N A Power wiring complete and in accordance with nameplate rating on Multistack unit and prepared for connec tion in ac...

Страница 31: ...ED _____ CONDENSER _____ 6 Operation of flow or differential switches with reduction of 50 P___________ 8 Condenser 3 way by pass valve YES NO Ifyes Temperaturesetpoint _____ F 9 System strainers inst...

Страница 32: ...sh PRG UP but tons Measured Readings 1 CHW P Drop______________________ 2 CW P Drop_______________________ Factory Setup 1 ProgramType___________________ 2 ChillerType____________________ 3 Refrigeran...

Страница 33: ...elow the LCHW Set point that compressors are staged on and off 3 The LCHW Stage Off delay is defaulted to 30 seconds with a 5 to 180 second range This allows for a delay between the shutting off of co...

Страница 34: ...er set point and system cleanliness Standard operating conditions with 95 F leaving condenser water and 45 F leaving chilled water temperature are discharge pressure at 325 psig 102 F saturated and su...

Страница 35: ...pes 4 Slowly open the top butterfly gate valve allowing water to flow through the condensers and onto the floor for approximately 30 seconds This will push out any debris trapped in the bottom of the...

Страница 36: ...ual maintenance requirements for Multistack Chillers involve proper shut down of the machine and cleaning of the heat exchangers The Preventative Maintenance bulletin MAINT 002 0416 and Heat Exchanger...

Страница 37: ...uction sensor Check set points in system variables Check for flow restriction Waiting For Condenser Water Flow Check CW pump Check flow switch operation Check filter strainers CheckTB11 inputs 3 8 Com...

Страница 38: ...Date Status Suct Press Head Press Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 System Ent Chw Lvg Chw Ent CW Lvg CW Demand Ca...

Страница 39: ...Date Status Suct Press Head Press Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 System Ent Chw Lvg Chw Ent CW Lvg CW Demand Ca...

Страница 40: ...MS IOM 001 0317 Supersedes MS IOM 001 0117 FWB 1065MapleAvenueP O Box510Sparta WI54656 Phone608 366 2400 info multistack com www multistack com...

Отзывы: