13
The uncertainties are expressed in % of the reading (R) and in number of
display points (pt): ±(a% R + b pt)
3.2. ELECTRICAL CHARACTERISTICS
3.3.1. VOLTAGE
DC range
4V
40V
400V
600V
Resolution
1mV
10mV
100mV
1V
Intrinsic
uncertainty
±(0.8% R ±3 pt)
Input
resistance
10MΩ
For AC measurements, the frequency is between 40 and 400Hz and the signal
is sinusoidal.
AC range
4V
40V
400V
600V
Resolution
1mV
10mV
100mV
1V
Intrinsic
uncertainty
±(1% R ±5 pt)
Input
resistance
10M
W
3.3.2. FREQUENCY
Measurement range: 10Hz to 10kHz.
Overload protection up to 600 Vac.
Input voltage
≥
2 V
ac
. This voltage increases with the frequency to be measured.
Range
100 Hz
1 kHz
10 kHz
Resolution
0,01 Hz
0,1 Hz
1 Hz
Intrinsic uncertainty
± (1% R ± 5 pt)
3.3.3. DUTY CYCLE
Measurement range
0.1-99.9%
Resolution
0.1%
Intrinsic uncertainty
±2%
3.3.4. CURRENT
The frequency is between 50 and 60Hz and the signal is sinusoidal.
Maximum current: 120% of the range for less than 60 seconds.
AC range
40A
400A
600A
Resolution
10mA
100mA
1A
Intrinsic
uncertainty
±(2.5% R ±5 pt)
3.3.5. RESISTANCE
Open-circuit voltage: approximately 0.4 V
dc
.
Range
Resolution
Intrinsic uncertainty
400
W
0,1
W
±(1% R ±5 pt)
4k
W
1
W
40k
W
10
W
400k
W
100
W
4M
W
1k
W
40M
W
10k
W
±(2% R ±5 pt)