182 – AL CAN Wrong Parameters
ZKP-Number: 2.0500.682
Incorrect parameters on CAN
Yellow alarm; warning
Cause
Corrective action
Wrong parameter value entered
in data record.
u
Contact Service.
183 – AL CAN No PU-Data
ZKP-Number: 2.0500.683
CAN PU data not present or available
Yellow alarm; warning
Cause
Corrective action
The selected CAN mode
initializes communication by
means of the application
environment data module. A
faulted occurred during an
attempt to copy a received data
module to the engine governor.
1. Check devices connected to CAN.
2. Contact Service.
184 – AL CAN PU-Data Flash Error
ZKP-Number: 2.0500.684
CAN PU data flash error
Cause
Corrective action
A program fault occurred while
trying to copy a received PU
data module into the flash
module.
u
Contact electronic Service.
186 – AL CAN1 Bus Off
ZKP-Number: 2.0500.686
CAN controller 1 is in "Bus-Off" status
Yellow alarm; automatic changeover to CAN 2
Cause
Corrective action
Short circuit, massive
interference or Baud rate
incompatibility.
1. Check CAN bus for short circuit, rectify short circuit as
necessary.
2. Check shielding, improve shielding as necessary.
3. Contact Service.
86 | Troubleshooting | MS150067/02E 2014-04
TIM-ID: 0000045495 - 001