361 – AL Power Stage Low
ZKP-Number: 1.8004.496
Internal electronic fault
Red alarm; engine shutdown possible
Cause
Corrective action
Electronics faulty.
1. Start ITS.
2. Replace engine governor if required.
3. Check additional messages if ITS indicates diagnosis
"Electronics OK" (e.g. wiring faulty).
4. Check solenoid valve wiring.
5. Contact Service.
362 – AL Power Stage high
ZKP-Number: 1.8004.497
Internal electronic fault.
Red alarm; engine shutdown possible
Cause
Corrective action
Electronics faulty.
1. Start ITS.
2. Replace engine governor if required.
3. Check additional messages if ITS indicates diagnosis
"Electronics OK" (e.g. wiring faulty).
4. Check solenoid valve wiring.
5. Contact Service.
363 – AL Stop Power Stage
ZKP-Number: 1.8004.560
Internal electronic fault.
Red alarm; engine shutdown
Cause
Corrective action
Electronics faulty.
1. Start ITS.
2. Replace engine governor.
3. Check additional messages if ITS indicates diagnosis
"Electronics OK" (e.g. wiring faulty).
4. Check solenoid valve wiring.
5. Contact Service.
110 | Troubleshooting | MS150067/02E 2014-04