Inclined positions, standard oil system (reference: waterline)
Number of cylinders
16
Longitudinal inclination, continuous max. driving end bottom (option: max.
operating inclination positions)
L
Degrees (°)
5
Longitudinal inclination, continuous max. driving end top (option: max. op-
erating inclination positions)
L
Degrees (°)
5
Transverse inclination continuous max. (option: max. operating inclination
positions)
L
Degrees (°)
10
Table 89: Inclined positions, standard oil system (reference: waterline)
Capacities
Number of cylinders
16
Engine coolant capacity, engine side (without cooling system)
R
Liters
70
Charge-air coolant, engine side
R
Liters
-
Fuel, engine side
R
Liters
6
Engine oil capacity, initial filling (standard oil system) (option: max. operat-
ing inclination positions)
R
Liters
114
Oil change quantity max. (standard oil system) (option: max. operating in-
clination positions)
R
Liters
102
Table 90: Capacities
Fan / fan cooler
Number of cylinders
16
Fan, push-type
X
Fan drive: mechanical via V-belt
X
Table 91: Fan / fan cooler
Sound
Number of cylinders
16
Exhaust noise, not attenuated - DL (free-field sound pressure level Lp, 1 m
distance, ISO 6798, +3 dB(A) tolerance)
R
dB(A)
114
Exhaust noise, not attenuated - DL (sound power level LW, ISO 6798,
+3 dB(A) tolerance)
R
dB(A)
126
Engine surface noise with attenuated intake noise (filter) - DL (free-field
sound power level Lp, 1 m distance, ISO 6798, +2 dB(A) tolerance)
R
dB(A)
102
Engine surface noise with attenuated intake noise (filter) - DL (sound pow-
er level LW, ISO 6798+2 db(A) tolerance)
R
dB(A)
120
Table 92: Sound
MS150118/01E 2015-05
| Technical Data | 49