background image

Honeywell

M9484 AND M9494 MODUTROL MOTORS ARE LOW
VOLTAGE, REVERSING PROPORTIONAL CONTROL
ACTUATORS FOR VALVES, DAMPERS AND AUXIL-

IARY EQUIPMENT. THEY ARE ESPECIALLY DE-
SIGNED 

 

GAS BURNER CONTROL SYSTEMS.

•i Replace M941 motors.

Oil immersed motor and gear train for reliable per-

formance and long life.

Wiring box provides NEMA 3 weather protection.

Actuator motor and circuitry operate from 24 volts

AC. Models available with factory installed transformer,
or internal transformer can be field added.

Quick-connect terminals standard   screw terminal

adapter available.

Cl Adapter bracket for matching shaft height of older

motors is standard with replacement motors.

Field adjustable stroke 

 to 

 models avail-

able.

Nominal timing of 30 seconds for 

 and 60 sec-

onds for 

 stroke is standard. Other timings are

available.

 Die-cast magnesium housing.

Available accessories include valve and damper

linkages, explosion proof housing, and auxiliary

,

switches.

Field addable interface modules can be mounted in

wiring box to upgrade actuator to Series 70 (electronic)
control.

•i Models available with tapped output shaft.

 M9484 rated for 150 lb.-in. torque at stan-

dard timings.

 M9494 rated for 300 lb.-in. torque at 2 or 4

minute timings for 

 stroke.

S.M. Form Number 63-2195-l
Rev. 11-90 @Honeywell Inc. 1990

Содержание M9481

Страница 1: ...minal adapter available Cl Adapter bracket for matching shaft height of older motors is standard with replacement motors 0 Field adjustable stroke 90 to 160 models avail able q Nominal timing of 30 seconds for 90 and 60 sec onds for 160 stroke is standard Other timings are available 0 Die cast magnesium housing q Available accessories include valve and damper linkages explosion proof housing and a...

Страница 2: ... position of shaft changes with adjustment of stroke Midpoint of stroke remains fixed as stroke is adjusted as shown in Fig 2 Stroke is adjusted by means of cams located in wiring compartment See Stroke Setting Procedure Motors are shipped with stroke set at 90 DEAD WEIGHT LOAD ON SHAFT Power or Auxiliary End 200 lb 90 8 kg maximum Maximum Combined Load 300 lb 136 kg AMBIENT TEMPERATURE RATINGS Ma...

Страница 3: ...s terminals Transformers mounted internally provide 24 Vat power to motor 198162JA 24 Vat 50 60 Hz for electrical iso lation 198162EA 120 Vat 50160 Hz 198162GA 220 Vat 50160 Hz 198162Al 120 208 240 Vat 50160 Hz Q7130A Interface Module with selectable voltage ranges 4 7 Vdc 6 9 Vdc and 10 5 13 5 Vdc Adapts motor to M71 XX function Q7230A Interface Module selectable voltage or cur rent control with ...

Страница 4: ...8A adapter bracket for mounting on these surfaces Allow enough clearance for installing accessories and servicing the motor when selecting a location See Fig 1 If located outdoors mount upright and use liquid tight con 4 duit connectors with wiring box to provide NEMA 3 weather protection MOUNTtNG Always install motors with the crankshaft horizontal Mounting flanges extending from the bottom of th...

Страница 5: ...The bracket is first mounted to the equipmel with standard bolts The motor is then mounted to the bracket using the bolts provided with the bracKet which thread into the threaded bracket holes DAMPER LINKAGES A 220738A Adapter Bracket is packed with replace ment motors Use of this bracket is optional for many damper applications but may be needed in damper appli cations requiring the crank arm to ...

Страница 6: ... and also may be added to all models Access to the wiring compartment is gained byremovingthe4screws inthetoppf the wiring box and lifting off the cover WIRING Disconnect power supply before wiring to prevent electri cal shock or equipment damage All wiring must agree with applicable codes ordinances and regulations A transformer is required to supply 24 Vat power to the motor Make sure that the p...

Страница 7: ...AD REDLEAD 2 n n 1 WIRING SHOULD BE NEC CLASS 1 UNLESS POWER SUPPLY MEETS CLASS 2 REQUIREMENTS TAPE UNUSED LEADS MAKE CERTAIN THE CURRENT DRAW OF THE EXTERNAL CIRCUIT IS LESS THAN CONTACT RATING OF SWITCH 1A n 2 ON TWO SWITCH MOTORS SECOND SWITCH HAS BLACK LEADS WITH BLUE YELLOW AND RED TRACERS M 254 I FIG 6 AUXILIARY SWITCH INTERNAL WIRING MINIMUM STROKE ADJUSl zTloN CAMS YELLOW I INNER AUXILIARY...

Страница 8: ... High Fire Position aViewed from power end of motor bSee Fig 9 TABLE 2 CAM MOTOR MAKES BREAKES POSITIONb POSITION Red Red High portion of cam Closing to to not in Contact Yellow Blue with Cam follower Red Tracer Red Tracer High portion of cam Opening to to in Contact Blue Tracer Yellow Tracer with Cam follower STROKE SEl lING On M94XXD E F motors stroke is field adjustable and can be set from 90 t...

Страница 9: ... M 3 3A PROVIDE BETTER VIEW OF BACK CAM M305 FIG 8 STROKE ADJUSTMENT SETUP l 8 IN STRAIGHT BLADE SCREWDRIVER STROKE ADJUST CAMS YELLOW RIGHT INNER INNER AUXILIARY CAM BLUE OUTER AUXILIARY CAM RED A 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REOUIRED A 2 TRANSFORMER MAY BE EXTERNAL OR INTERNAL M 315c POWER END OTOR CLOSE NOTE CAMS ARE OFFSET VERTICALLY TO PROVIDE BETTER VIEW...

Страница 10: ...eter with R W B terminals on pot connected to corresponding terminals on motor Fig 9 3 Adjust 135 ohm pot so that motor shaft turns to position where auxiliary equipment is to be switched 4 Insert a l 8 in straight blade screwdriver into slot on cam associated with selected auxiliary switch The inner blue cam actuates the inner right switch the outer red cam actuates the outer left switch MOVE TOP...

Страница 11: ...INIMUM POSITION PO TENTIOMETER ETC SERIES 99 CONTROLLER MOTOR OPTIONAL CONNECTIONS WITH 2 135 OHM POTENTIOMETERS IN SERIES SERIES 90 CONTROLLER MOTOR SERIES 90 HIGH LIMIT CONTROL TRANSFORMER n 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AN OVERLOAD PROTECTION AS REQUIRED n 2 TRANSFORMER MAY BE INTERNAL OR EXTERNALTO MOTOR E2rM4 IG 1 l MOTOR USED WITH ASERIESSO CONTROI LER AND A SERIES 90 LOW OR HIGH L...

Страница 12: ...ition NOTES a Ensure motor transformer is sized properly If a common transformer is used to power multiple motors ensure power input is in phase with all motors b Motors may operate in Series 90 or two position control applications However checking voltage between terminals R to B and R to W is necessary to confirm proper operation in electronic W973 4 to 20 mA etc applications DAMPER APPLICATION ...

Отзывы: