INM5000-6
Jul 2010
6.7.3
Testing
Make the safe- and hazardous-area connections shown in figure 6.15
and check the status of the output contacts for each channel in turn (with
a 22k
Ω
resistor connected to the other channel) as shown in table 6.6.
Table 6.6
6.8
MTL5018 single-pole, changeover
relay, two-channel, switch/proximity
detector with line fault detection and
phase reversal
The MTL5018 modules enable each of two safe-area loads to be relay-
controlled by switches or proximity detectors in a hazardous area. Line
fault detection (LFD) and output phase reversal (see 3.1.3) facilities are
included.
6.8.1
Wiring connections
See figure 6.16 for wiring connections.
Note:
Reactive loads must be adequately suppressed.
6.8.2
Line fault detection
(See section 3.1.4 for definition of a line fault)
On each channel, input line faults (open- or short-circuit) are indicated
by an LED and the de-energising of the output.
LFD is enabled/disabled by switches located on the top of the module.
Note that if the LFD facility is enabled for switch inputs, the resistors
shown in figures 6.16 and 6.17 MUST be fitted.
6.8.3
Testing
Make the safe- and hazardous-area connections shown in figure 6.17
and check the status of the output contacts for each channel in turn (with
a 22k
Ω
resistor connected to the other channel) as shown in table 6.7.
6.9
MTL5018AC single-pole, changeover
relay, two-channel, switch/proximity
detector with line fault detection and
phase reversal
The MTL5018AC modules enable each of two safe-area loads to be
relay-controlled by switches or proximity detectors in a hazardous area.
Line fault detection (LFD) and output phase reversal facilities are included
(see section 3.1.3 ).
6.9.1
Wiring connections
See figure 6.18 for wiring connections.
Note:
Reactive loads must be adequately suppressed.
6.9.2
Line fault detection
(See section 3.1.4 for definition of a line fault)
On each channel, input line faults (open- or short-circuit) are indicated
by an LED and the de-energising of the output. LFD is enabled/disabled
by switches located on the top of the module.
Note
that if the LFD facility is enabled for switch inputs, the resistors
shown in figures 6.18 and 6.19 MUST be fitted.
Terminal
Function
1
Input –ve (Ch 1)
2
Input +ve (Ch 1)
3
Earth leakage detection
4
Input –ve (Ch 2)
5
Input +ve (Ch 2)
7
Line fault detection
8
Output (Ch 2)
9
Output (Ch 2)
10
Line fault detection
11
Output (Ch 1)
12
Output (Ch 1)
13
Supply –ve
14
ve
6
5
4
3
2
1
7
8
9
10
11
12
13
14
LFD
Vs
Vs+
20 to 35V dc
Ch 2
Ch 1
LFD
LFD
To earth leakage
detector
SW
22k
W
680
W
a
b
c
open
22k
W
+
Ch1
Ch2
+
Output
Line-fault
Input
relay
relay
(11-12, 8-9)
(7 & 10)
Open-circuit
Open
Open
Short-circuit
Closed
Open
680
Ω
Closed
Closed
22k
Ω
Open
Closed
Terminal
Function
1
Input –ve (Ch 1)
2
Input +ve (Ch 1)
3
Earth leakage detection
4
Input –ve (Ch 2)
5
Input +ve (Ch 2)
6
Earth leakage detection
7
Normally-closed contact (Ch 2)
8
Common (Ch 2)
9
Normally-open contact (Ch 2)
10
Normally-closed contact (Ch 1)
11
Common (Ch 1)
12
Normally-open contact (Ch 1)
13
Supply –ve
14
ve
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
Ch 2
Ch 1
To earth leakage
detector
SW
22k
W
680
W
a
b
c
open
22k
W
+
Ch1
Ch2
+
Figure 6.15:
Test circuit for MTL5017
Figure 6.17:
Test circuit for MTL5018
6
5
4
3
2
1
7
8
9
10
11
12
13
14
LFD
Vs
Vs+
20 to 35V dc
To earth
leakage
detector
22k
W
680
W
+
Ch 2
22k
W
680
W
+
Ch 1
LFD
LFD
For contact inputs
resistors must be fitted
Figure 6.14:
MTL5017 wiring diagram and connections
Hazardous area
Safe area
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
To earth leakage
detector
22k
W
680
W
+
22k
W
680
W
+
Resistors required only
for line fault detection
Ch 2
Ch 1
Figure 6.16:
MTL5018 wiring diagram and connections
Hazardous area
Safe area
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание MTL5000 Series
Страница 42: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 43: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 44: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...