6.11
MTL5022 loop-powered
solenoid/alarm driver, IIB
The MTL5022 enables a device located in the hazardous area to be
controlled by a switch located in the safe area. Suitable for IIA and IIB
applications.
6.11.1
Wiring connections
See figure 6.22 for wiring connections.
6.11.2
Testing
Make the safe- and hazardous-area connections shown in figure 6.23,
apply 24V to terminals 11 and 12 and, with no load, check voltage and
short-circuit current levels at terminals 1 and 2 as follows
18
INM5000-6
Jul 2010
6.12
MTL5023 solenoid/alarm driver with
line fault detection and phase reversal
The MTL5023 enables a device located in the hazardous area to be
controlled by a volt-free contact or logic signal located in the safe area.
Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities
are included.
6.12.1
Wiring connections
See figure 6.24 for wiring connections.
6.12.2
Line fault detection
(See section 3.1.4 for definition of a line fault)
Hazardous-area line faults are signalled to the safe area by an LED and
a solid-state switch which de-energises when a line is open- or short-
circuited.
6.12.3
Testing
Make the safe- and hazardous-area connections shown in figure 6.25
and carry out the voltage and current checks as shown in table 6.8.
Input
Status
Output
Short-circuit
voltage
LED
voltage
current
(terminals 11 & 12) yellow (terminals 1 & 2)
(terminals 1 & 2)
24V dc
On
22 to 24V
–
24V dc
On
–
61 to 70mA
Terminal
Function
1
Output –ve
2 Output
+ve
3
Earth leakage detection
11
Supply –ve
12
ve
7
8
9
10
11
12
6
5
4
3
2
1
24Vdc
+
+
V
A
Figure 6.23:
Test circuit for MTL5022
7
8
9
10
11
12
6
5
4
3
2
1
Solenoid, alarm or
other IS device
To earth
leakage
detector
20 35Vdc
+
+
Hazardous area
Safe area
Figure 6.22:
MTL5022 wiring diagrm and connections
Input switch
LFD
Status
Output
Output
SW1
Phase reverse
LED
LED
voltage
current
(terminals 11 & 12)
Load
switch
(red)
(yellow)
(terminals 1 & 2)
(terminals 1 & 2)
Closed
2k
Ω
Normal
Off
On
>19.5V
–
Open
2k
Ω
Normal
Off
Off
<4.5V
–
Closed
15k
Ω
Normal
On
On
>21.0V
–
Open
15k
Ω
Normal
On
Off
<7.0V
–
Closed
Short-circuit
Normal
On
On
–
>45mA
Open
Short-circuit
Normal
On
Off
–
<6mA
Closed
Short-circuit
Reverse
On
Off
–
<6mA
Table 6.8
Vs
Vs+
20 to 35V dc
Line fault
detection
+
+
Test meter
(set initially
to volts)
Load
+
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Solenoid, alarm or
other IS device
To earth
leakage
detector
+
Vs
Vs+
20 to 35V dc
Line fault
detection
+
+
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Figure 6.24:
MTL5023 wiring diagram and connections
Figure 6.25:
Test circuit for MTL5023
Hazardous area
Safe area
Terminal
Function
1
Output –ve
2
ve
3
Earth leakage detection
7
Line fault signal -ve
10
Line fault ve
11
Control –ve
12
Cve
13
Supply –ve
14
ve
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание MTL5000 Series
Страница 42: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 43: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 44: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...