26
INM5000-6
Jul 2010
6.25.2 Testing
Make the safe and hazardous-area connections shown in figure 6.56
and, substituting appropriate resistors at R
test
, carry out the following
checks.
6.26
MTL5061 two-channel loop-powered
fire/smoke detector interface
The MTL5061 isolates two conventional fire and smoke detectors located
in hazardous areas. The triggering of a detector causes a
corresponding change in the safe-area circuit. The unit has reverse input
polarity, and 'non-fail' earth fault detection on either line can be
provided.
6.26.1
Wiring connections
See figure 6.59 for wiring connections.
6.26.2
'No-fail' earth fault protection
Protection is enabled by connecting earth leakage detectors, such as
MTL2220s (not CE marked), to the MTL5061; via terminal 3 or 6, or
both. To maintain isolation between the two channels, separate earth
leakage detectors are required. If a fault on either line of each channel
is detected, the unit continues working.
Note:
The MTL2220 introduces a 100µA, 1Hz ripple to the field circuit.
6.26.3
Testing
Make the safe- and hazardous-area connections shown in figure 6.60
and, using RV1 to vary the output current, carry out the following check
for both channel 1 and channel 2:
6.27
MTL5074 temperature converters,
THC or RTD input
The MTL5074 converts low-level signals from temperature sensors
located in a hazardous area into 4 to 20mA signals for driving safe-area
loads.
Note
: The earlier model MTL5073 had an internal link between
terminals 11 and 13. The MTL5073 model is discontinued.
6.27.1
Wiring connections
See figure 6.61 for wiring connections.
Note:
for THC inputs requiring cold-junction compensation, a HAZ-CJC
hazardous-area connector (with integrated CJC sensor) is required not a
HAZ1-3 signal plug.
6
5
4
3
2
1
7
8
9
10
11
12
I
I
I
I
Ch 2 Fire detectors
+
To earth leakage
detector
Ch 1 Fire detectors
+
6 to
35V dc
6 to
35V dc
Ch 2
Ch 1
+
+
Figure 6.59:
MTL5061 wiring diagram and connections
Hazardous area
Safe area
Output
Current
current
reading
(A2)
(A1)
10 to 40mA
<±400µA
6
5
4
3
2
1
7
8
9
10
11
12
I
I
I
I
Ch 2
+
+
Ch 2
24V
+
A1
A2
Ch 1
180
W
2k
RV1
W
+
+
Figure 6.60:
Test circuit for MTL5061
Hazardous area
Safe area
Figure 6.61:
MTL5073/74 wiring diagram
7
8
9
10
11
12
13
14
6
5
4
3
2
1
mV
I
Vs
Vs+
20 to 35V dc
+
mV
Load
4-wire
3-wire
+
4/20mA
MTL5053
PWR
TERMINA
TOR
Figure 6.58:
Top label, MTL5053
Voltage across
R
test
terminals 2 and 1 (V
1
)
Open-circuit
17.8 < V
1
<19V
220
Ω
11.5V <V
1
<13.5V
10
Ω
V
1
<5V
6
5
4
3
2
1
7
8
9
10
11
12
13
14
T
V
V
Vs+
Vs
20 to 35V dc
R
test
V
1
+
Figure 6.57 :
Test circuit for MTL5053
Terminal
Function
1
THC/EMF/RTD input –ve
3
THC/EMF/RTD input +ve
4
3-wire RTD input –ve
5
4-wire RTD input +ve
11
Output –ve
12
ve
13
Supply –ve
14
ve
Terminal
Function
1
Output –ve (Ch 1)
2
ve (Ch 1)
3
Earth leakage detection (Ch 1)
4
Output –ve (Ch 2)
5
ve (Ch 2)
6
Earth leakage detection (Ch 2)
8
Input –ve (Ch 2)
9
Input +ve (Ch 2)
11
Input –ve (Ch 1)
12
Input +ve (Ch 1)
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание MTL5000 Series
Страница 42: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 43: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 44: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...