Note:
the open circuit window (between 350µA and 50µA) is not
hysteresis, all MTL5000 Series modules with inputs conforming to
NAMUR/DIN 19234 will switch between open and complete circuit
conditions within these limits.
Note:
the short circuit window (between 100
Ω
and 360
Ω
) is not
hysteresis, all MTL5000 Series modules with inputs conforming to
NAMUR/DIN 19234 will switch between open and complete circuit
conditions within these limits.
Modules with LFD and inputs conforming to NAMUR/DIN
19234:
MTL5011B, 5014* and 5018: LFD enable switch on top label
* The MTL5014 has a Slave/LFD output relay arrangement
(see module description in section 6).
MTL5012 and 5015: LFD enable switch on top label
MTL5017: LFD permanently enabled
Other modules with LFD facility
MTL5023 solenoid/alarm driver: LFD automatic
MTL5046 isolating driver: LFD automatic
Note:
The safe-area circuit impedance will increase with hazardous-
area load and will rise >150k
Ω
for the 'open circuit' line fault.
MTL5113x: LFD automatic
Hazardous-area load
Safe-area input
<50
Ω
High impedance (>150k
Ω
)
>90
Ω
Normal operation
Hazardous-area input (either channel)
Line-fault-detect relay
<50µA
De-energised
>350µA
Energised
>360
Ω
Energised
<100
Ω
De-energised
LFD switch setting
Hazardous-area input(s)
Solid-state output(s)
On
<50µA
Non-conducting
On
>350µA
Conducting
On
>360
Ω
Conducting
On
<100
Ω
Non-conducting
LFD switch setting
Hazardous-area input(s)
Output relay(s)
On
<50µA
De-energised
On
>350µA
Energised
On
>360
Ω
Energised
On
<100
Ω
De-energised
3.1.3
Phase reversal
Switch(es) to change the phase of the output(s) relative to the input(s) are
provided on the top labels of some of the MTL5000 Series modules and
on the base of others. The following applies:
MTL5011B, 5014 and 5018: Phase reversal switch on top label
MTL5017: Phase reversal switch on base of module
MTL5012 and 5015: Phase reversal switch on top label
MTL5023 and 5024: Phase reversal switch on base of module
Positions for base-located switches are set as shown in figure 3.4.
3.1.4
Line fault detection (LFD)
Line fault detection on hazardous-area sensor lines (open circuit or short
circuit) is provided on some MTL5000 Series modules.
Note:
resistors must be fitted when using the LFD facility with a contact
input: 500
Ω
to 1k
Ω
in series with switch and 20k
Ω
to 25k
Ω
in parallel
with switch.
For hazardous-area inputs conforming to NAMUR/DIN
19234, a line fault condition is indicated as follows:
Open circuit condition if hazardous-area current <50µA
Line integrity (no open circuit) if hazardous-area current >350µA
Short circuit condition if hazardous-area load <100
Ω
Line integrity (no short circuit) if hazardous-area load >360
Ω
A
B
2
1
Normal
Reverse
CH1
CH2
Label face
Base of unit
3
INM5000-6
Jul 2010
PR switch setting
Hazardous-area input(s)
Output relay(s)
Off
<1.2mA
De-energised
Off
>2.1mA
Energised
On
<1.2mA
Energised
On
>2.1mA
De-energised
PR switch setting
Hazardous-area input(s)
Solid-state output(s)
Off
<1.2mA
Non-conducting
Off
>2.1mA
Conducting
On
<1.2mA
Conducting
On
>2.1mA
Non-conducting
Hazardous-area
PR switch setting
Safe-area control
output
o
←
(off)
CTRL+Ve >4.5V above CTRL-Ve
Enabled
o
←
(off)
CTRL+Ve <1.4V above CTRL-Ve
Disabled
→
+ (on)
CTRL+Ve >4.5V above CTRL-Ve
Disabled
→
+ (on)
CTRL+Ve <1.4V above CTRL-Ve
Enabled
Hazardous-area load
Solid-state LFD output
<50
Ω
Non-conducting
>7k
Ω
Non-conducting
Hazardous-area input
LFD output
< 50µA (open-circuit)
de-energised
> 6.6mA (short-circuit)
de-energised
Figure 3.4:
Phase reversal switch on base of units
PR switch setting
Hazardous-area input(s)
Output relay(s)
o
←
(off)
<1.2mA
De-energised
o
←
(off)
>2.1mA
Energised
→
+ (on)
<1.2mA
Energised
→
+ (on)
>2.1mA
De-energised
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание MTL5000 Series
Страница 42: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 43: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 44: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...