Installation

2. Installation

2.1

Location of the FMK 9002

The following aspects must be taken into consideration before locating the FMK 9002:

-

Location close to the hazardous area and for personal monitoring applications at head level

-

Property of the target gas, e.g. lighter or heavier than air

-

Protection against sunlight, spray water, rain, and dust

-

Free access for maintenance personnel 

For narrow monitoring locations a sensor extension is available as an option.

2.2

Mounting the FMK 9002

As a standard accessory a wall mounting support is delivered with the FMK 9002. At the monitoring 
point the wall mounting support is fixed to the wall with four screws (M5), with the black locking knob on
top and facing the FMK 9002.

Finally, the FMK 9002 is affixed to the wall mounting support.

2.3

Connecting  the FMK 9002

Connect the two wires of the cable fixed to the FMK 9002 with the two-wire cable leading to the 
Central Controller FMS 8700 or FMS 8710. 

If the FMK 9002 is connected to other 4 ... 20 mA Central Control Systems, the limit values for the 
power supply (7.5  ... 15 V) must be observed. 

Pay attention to the correct polarity of the two-wire cable !

A watertight junction box is recommended for connection. The maximum length of the two-wire cable 
is subject to the technical specifications of the type of cable used as well as to the capacitance values
stated in the ex-proof certificate. 

The following applies in combination with the Central Controller FMS 8700  or 8710:

Version

Cable diameter

Distance

standard 

2 x 0.5   mm

2

3.6 km

2 x 0.75 mm

2

5.4 km

intrinsically safe

2 x 0.5   mm

2

0.8 km

2 x 0.75 mm

2

1.2 km 

With the intrinsically safe version of the Central Controller FMS 8700  and FMS 8710, the maximum 
allowable capitance of 190 nF/km at the ex-separator must be observed. 

A type of cable with f.i. 200 nF/km, allows a maximum cable length of 0.95 km. 

Содержание FMK 9002

Страница 1: ...ithout notice Print No 9002 0000 61 0D 05 2004 Guide to Operation Remote Sensor Head FMK 9002 MST Technology GmbH Benediktstr 1 82069 Hohensch ftlarn Germany Fon 49 0 8178 8690 Fax 49 0 8178 8220 www...

Страница 2: ...Alarms at the Central Controller FMS 8700 5 3 3 Operating Modes 5 3 4 Functional Test and Scaling External Control Systems 6 3 4 1 4 mA Simulation Zero 6 3 4 2 20 mA Simulation full scale 6 4 Sensor...

Страница 3: ...meter 7 Span Adjustment Potentiometer Operational Elements for Instrument Functions and 4 20 mA Interface Test 8 Selector Switch for Operating Modes 9 LED Indication for Operating Modes 10 Push Button...

Страница 4: ...K 9002 Connect the two wires of the cable fixed to the FMK 9002 with the two wire cable leading to the Central Controller FMS 8700 or FMS 8710 If the FMK 9002 is connected to other 4 20 mA Central Con...

Страница 5: ...700 To prevent that alarm relays are activated and external alarms are released during electrical or gas technical checks the EXT ALARMS key switch at the Central Controller FMS 8700 must be set to th...

Страница 6: ...he 4 20 mA loop is 4 mA Zero is indicated at the FMK 9002 and FMS 8700 8710 s displays Alarm is not activated at the FMS 8700 or FMS 8710 except with instruments for oxygen deficiency 3 4 2 20 mA Simu...

Страница 7: ...sure to align the orientation guide properly before pushing the sensor into place Write down the concentration value CE stated on the sensor Screw in the sensor cap Perform calibration procedure 4 1...

Страница 8: ...r oxygen Place the calibration cap P N 8600 4002 over the sensor and start the calibration gas flow flow volume approx 18 l h or 300 ccm min Allow the reading on the digital display to stabilize Turn...

Страница 9: ...e performed in gas free atmosphere Selected FMK 9002 operating mode is calibrating Zero adjustment according to section 5 1 Press and hold button 20 mA CE Value calibration current will be fed Turn th...

Страница 10: ...__ Sensor Adaptor standard 9002 0150 Sensor Cap standard 9002 0151 Test Plug package of ten 5 STEST 01K Calibration Cap standard 8600 4200 Wall Mounting Support 8601 0040 Guide to Operation German 900...

Страница 11: ...0 Cl2 Chlorine 0 5 00 ppm 9012 5301 CO Carbon Monoxide 0 1000 ppm 9002 5400 COCl2 Phosgene 0 1 00 ppm 9012 6600 F2 Fluorine 0 5 00 ppm 9012 6400 GeH4 Germane 0 5 0 ppm 9012 6900 H2 Hydrogen 0 0 500 90...

Страница 12: ...ib I BVS Nr 92 C 1003 Approved to meet the Intrinsic Safety Standard EEx ib IIC T6 BVS Nr 92 C 2002 Approved to meet the European Safety Standards EN 50014 and EN 50020 Copies of these approvals are...

Страница 13: ...FMK 9002 9002 0000 61 0E 05 04 page 13 Certificates...

Страница 14: ...FMK 9002 9002 0000 61 0E 05 04 page 14 Certificates...

Страница 15: ...FMK 9002 9002 0000 61 0E 05 04 page 15 Certificates...

Страница 16: ...FMK 9002 9002 0000 61 0E 05 04 page 16 Certificates...

Страница 17: ...FMK 9002 9002 0000 61 0E 05 04 page 17 Certificates...

Страница 18: ...FMK 9002 9002 0000 61 0E 05 04 page 18 Certificates...

Отзывы: