Section 4 

ZGARD CX II Controller 
Operation and Features 

 

Note:

  The  ZGARD  CX  II  Programmable  Controller 

DOES  NOT  come  pre-programmed  with  any 
sensor,  relay  or  alarm  setpoint  parameters.  These 
must  be  field-programmed  and  verified  by  trained 
and authorized personnel. 

Auto  Configuration: 

The  ZGARD  CX  II  Controller 

will  automatically  recognize  the  number  of  remote 
gas  sensors  that  are  compliant  with  the  system. 
The  first  screen  on  the  configuration  setup  menu 
prompts the user to decide if the Auto-Configuration 
program should be executed. There are 3 options to 
choose  from.  The  Full  Configuration…  finds 
sensors  and  sets  all  parameters  to  defaults 
includi

ng  relay  assignments.  The  Add  Sensors… 

finds  new  sensors  beyond  the  last  active  sensor  in 
the  system.  The  Change  Sensors…  compares  the 
gas  identification  codes  of  all  active  sensors  and 
reconfigures  the  sensors  with  the  new  association. 
When  either  option  is  chosen,  the  controller  will 
start searching for the remote gas sensors residing 
on  the  RS485  data  bus  network  and  organizes  the 
system accordingly.  

Programmable Configuration:

 The Keypad on the 

front  panel  permits  the  user  to  program  the 
controller  for  customized  applications.  To  prevent 
unauthorized  access,  an  entry  code  must  be 
entered before the configuration mode is offered. 

Remote  Sensors: 

The  controller  is  designed  to 

host a series of MSA ZGARD S or GS gas sensors 
with  RS485  digital  output.  These  sensors  are 
supported  on  a  2-wire  data  bus  (network).  Each 
sensor  facilitates  Address  Jumpers  used  to  assign 
a digital address code.  

Caution  Condition: 

If  the  gas  level  measured  at 

any  of  the  remote  sensors  or  group  of  sensors 
exceeds  a  predetermined  caution  threshold,  then 
the  common  Caution  LED  located  above  the  LCD 

Screen  will  indicate  a  caution  event.  Relay  outputs 
can  be  pre-assigned  to  activate  on  the  caution 
level. 

Warning  Condition: 

If  the  gas  level  measured  at 

any  of  the  remote  sensors  or  group  of  sensors 
exceeds  a  predetermined  warning  threshold,  then 
the  common  Warning  LED  located  above  the  LCD 
Screen will indicate a warning event. Relay outputs 
can  be  pre-assigned  to  activate  on  the  Warning 
level. 

Alarm Condition: 

If the gas level measured at any 

of the remote sensors or group of sensors exceeds 
a predetermined alarm threshold, then the common 
Alarm  LED  located  above  the  LCD  Screen  will 
indicate an alarm event. The audible alarm will also 
sound at this time, pressing the reset button during 
an  Alarm  event  will  silence  the  audible  device.  If  a 
new  Alarm  should  occur  while  the  gas  controller  is 
already in an Alarm condition, the audible alarm will 
sound  again;  repeatedly  pressing  the  reset  button 
can silence it. Relay outputs can be pre-assigned to 
activate on the Alarm level. 

Relay  Mode:

  Each  programmable  relay  can  be 

configured  to  operate  in  the  normally  de-energized 
or  normally  energized,  latching  or  non-latching 
mode and an OFF Delay. 

System Diagnostics Feature: 

If any active remote 

device  should  fail  to  communicate  on  the  RS485 
network,  the  System  OK  LED  will  turn  OFF,  the 
FAULT  LED  will  turn  ON  and  the  fail  relay  will  de-
activate.  Subject  to  a  communication  failure,  the 
Warning  LED  will  also  turn  ON  and  the  warning 
relays  will  be  activated.  Considering  that  the 
warning  level of a gas controller system is typically 
used  as  the  ventilation  index,  this  feature  is 
provided  as  a  fail-safe  measure  to  ensure  the 
surveillance-affected area is ventilated. 

 
 

 
 
 
 
 
 
 
 
 
 
 

4.0

Содержание ZGARD CX II

Страница 1: ...ment avec ses instructions Comme tout appareil complexifi ce produit peut vous donner les r sultats anticip s seulement s il est install usag et que le service d entretien sont effectu s d apr s les i...

Страница 2: ...ufacturers of such components THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AND IS STRICTLY LIMITED TO THE TERMS HEREOF SELLER SPECIFICALLY DISCLAIMS ANY WARRANTY OF...

Страница 3: ...llation and as a routine inspection of the system 5 Use only genuine MSA replacement parts when performing any maintenance procedures provided in this manual Failure to do so may seriously impair inst...

Страница 4: ...ays 8 3 Section 9 Operation Configuration Set Up Menu Auto Configuration 9 0 Auto Configuration continued 9 1 Auto Configuration continued Caution Warning and Alarm setup 9 2 Zone Assignment External...

Страница 5: ...the operating alarm and fault diagnostic status of the system The display is split in two display mode sections Status Display Common LED s for System OK Green Caution Amber Warning Amber and Alarm Re...

Страница 6: ...etermine the capacity designation and number of remote gas sensors and configure the controller according to the required application Also refer to the ZGARD CX II controller Installation Outline draw...

Страница 7: ...1 500 meters away from the controller The ZGARD CX II Controller does NOT provide operating power for the Remote Relay Modules REMOTE RELAY MODULE SPECIFICATIONS Operating Power 17 27VAC 50 60 Hz or...

Страница 8: ...the remote sensors or group of sensors exceeds a predetermined caution threshold then the common Caution LED located above the LCD Screen will indicate a caution event Relay outputs can be pre assigne...

Страница 9: ...ntroller can then execute control functions based on each zone By adding optional Remote Relay Modules RRM s distributed control can be achieved in addition to the internal control via the relays insi...

Страница 10: ...y 1 42001 Relay 2 Etc 42039 Relay 40 The following data is available for each SENSOR 40xx0 Enable State Gas ID 0 Disabled 1 99 GasID 40xx1 Status 0 OK 1 Fail 2 Caution 4 Warning 8 Alarm 40xx2 Zone Ass...

Страница 11: ...ect Zone 1 8 511 518 No Sensors Zone 1 8 Multi State 101 199 Alarm State Sensor 1 99 201 299 Zone Assignment Sensor 1 99 301 399 RS 485 Port Sensor 1 99 401 499 GasID Sensor 1 99 Binary 1 40 Relay Sta...

Страница 12: ...es not scan the remote sensors and does not activate any warning or alarm relays An automatic timeout returns the ZGARD CX II to normal operation if no keypad activity is detected for 1 minute while i...

Страница 13: ...each their respective warning level then the sensor numbers will be displayed adjacent to the W descriptor Should the number of sensors in a warning condition exceed the physical space provided then a...

Страница 14: ...of remote sensors and is sequentially updated every 2 seconds Column1 The term ZONE reports the zone numbers Column2 The term SNS reports the number of sensors allocated to the current Zone Column3 Th...

Страница 15: ...9 3 2 1 1 O K 1 9 6 0 P P M C O A L A R M R G 1 0 0 P P M R G 1 0 0 C O 1 Z O N E S N S S T A T U S W 1 2 2 2 1 1 O K A 9 3 3 4 A L A R M 8 1 Section 8 ZGARD CX II Controller LCD Screen Display Featu...

Страница 16: ...ZRM is present for zone 2 1 4 0 P P M C O W A R N R G 1 0 0 P P M C Z O N E S N S S T A T U S W 1 4 W A R N A 2 4 W A R N 4 Sensor 1 60ppm alarm 2 45ppm warning Zone 1 ALARM because one or more sensor...

Страница 17: ...h is the default setting The third line implies the programmer to change the setting There are 3 options for the auto configuration program A U T O C O N F I G N O C H A N G E E N T E R A C C E P T Op...

Страница 18: ...e asked to verify the Warning and Alarm set points Press the menu key to accept and continue A U T O C O N F I G 24 S E N S O R S F O U N D 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 V E R I F Y W A...

Страница 19: ...WARNING SETPOINT menu will appear The second line of the display shows the current sensor to be assigned a warning set point level The sensor range is also shown for reference only The third line show...

Страница 20: ...E 0 1 R E S C A N E N T E R U P D A T E 17 2 As the ZGARD CX II scans for external relay cards it displays all cards that are found E X T E R N A L R E L A Y C A R D S A C T I V E 0 1 F O U N D 0 1 2...

Страница 21: ...hich this WARNING relay is assigned A relay may be assigned to multiple zones 20 1 Press the or key to move through all of the relay numbers 20 2 Press 1 through 8 to add or delete a zone that this WA...

Страница 22: ...ntil the desired mode appears 23 2 Next relay number Press the or key to move through all of the relay assignments R E L A Y O P E R A T I O N R E L A Y 1 I N T E R N A L R E L A Y 1 M O D E N O R M A...

Страница 23: ...L A Y F O R C A L I B R A T I O N S E N S O R 1 P O R T 1 R A N G E 1 0 0 P P M G A S L E V E L 0 P P M G A S C O S E N S O R R E F R E S H 3 S E C 32 Press the MENU key 33 The TIME SET menu will app...

Страница 24: ...0 0 F R A M E 8 N 1 M A C 0 0 1 N X T P R V 0 9 V A L U E E N T E R A C C E P T 36 4 Go to next parameter Press the or key to move through all of the desired parameters Not all parameters are changea...

Страница 25: ...Depending on the controller s warning alarm and delay settings the display status and the relay action of the controller may vary Refer to the installation sections of the associated ZGARD CX II Contr...

Страница 26: ...This page left blank...

Страница 27: ...P Zgard CX II ZGARD RRM Ratings Caution Configuration Labels ZGARD CX II B 0 Gas Monitoring Station Power 17 27VAC 50 60Hz or 24 38VDC 0 3Amp 0 7Amp with strobe AC only Input RS 485 99 ZGARD Sensors m...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Отзывы: