Section 10 

ZGARD CX II Controller 
Start-Up Procedure 
 
When  wiring,  checking  or  working  within  a  ZGARD  CX  II  Controller,  always  disconnect  the 
main power to prevent bodily harm. 

 

1.  Loosen the locking screws on front of the controller and open the door.  

2.  Locate the power switch on main circuit board inside controller enclosure. 

3.  Check all wiring connections are correct and secure. 

4.  Confirm  the  RS485  digital  remote  sensors  associated  with  the  controller  are  appropriately  assigned  a 

unique binary address code. 

Refer to the appropriate gas sensor manual for further details. 

 

5.  Power up the controller and observe the behavior of the following indicators; 

Green LED (SYSTEM OK) Indicator on front panel should be ON.  

Red LED (SYSTEM FAULT) Indicator on front panel should be OFF. 

Amber LED (CAUTION) Indicator should be OFF 

Amber LED (WARNING) Indicator on front panel should be OFF.

  

Red LED (ALARM) Indicator on front panel should be OFF. 

During initial power up of the controller, the local audible alarm may be activated, press RESET button 
to silence.  

 

6. 

Allow the associated remote gas sensors to stabilize. 

Refer to the ZGARD S or GS sensor manual for 

further details.  

 

Depending on the controller’s warning, alarm and delay settings, the display status and the relay action 
of the controller may vary. Refer to the installation sections of the associated ZGARD CX II Controller. 

 

7.  Confirm  the  functionality  of  the  controller  and  that  is  operating  according  to  the  designed  or  pre-set 

configuration settings. 

 

8. 

Apply  a  representative  sample  (at  least  60%  of  the  operating  range)  of  the  target  gas  to  each  of  the 
associated remote gas sensors. This simple test should drive  the  gas sensors upscale and simulate a 
warning and or an alarm condition on the controller. 

Refer to the ZGARD S or GS sensor manual for 

further details.   

 

During this procedure, the audible device may be activated, press RESET button to silence.  
The warning and alarm indicators and the corresponding relays may be activated. 

Depending on the controller’s warning and alarm set-points and delay feature settings, the Warning and 

Alarm relays may be activated.  

Any  remote  equipment,  which  may  be  connected  to  the  controller  relay  contacts,  should  now  be 
activated.  

 

9.  Remove any test equipment from the sensor and controller. 

10.  Secure the locking screws on the front door of the ZGARD CX II Controller. 

11.  Secure the locking screws on cover or front door of the associated remote gas sensors.  

 

The initial function test of the ZGARD CX II Controller is now completed.

 

 

 
 
 

 
 

10 

 

Содержание ZGARD CX II

Страница 1: ...ment avec ses instructions Comme tout appareil complexifi ce produit peut vous donner les r sultats anticip s seulement s il est install usag et que le service d entretien sont effectu s d apr s les i...

Страница 2: ...ufacturers of such components THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AND IS STRICTLY LIMITED TO THE TERMS HEREOF SELLER SPECIFICALLY DISCLAIMS ANY WARRANTY OF...

Страница 3: ...llation and as a routine inspection of the system 5 Use only genuine MSA replacement parts when performing any maintenance procedures provided in this manual Failure to do so may seriously impair inst...

Страница 4: ...ays 8 3 Section 9 Operation Configuration Set Up Menu Auto Configuration 9 0 Auto Configuration continued 9 1 Auto Configuration continued Caution Warning and Alarm setup 9 2 Zone Assignment External...

Страница 5: ...the operating alarm and fault diagnostic status of the system The display is split in two display mode sections Status Display Common LED s for System OK Green Caution Amber Warning Amber and Alarm Re...

Страница 6: ...etermine the capacity designation and number of remote gas sensors and configure the controller according to the required application Also refer to the ZGARD CX II controller Installation Outline draw...

Страница 7: ...1 500 meters away from the controller The ZGARD CX II Controller does NOT provide operating power for the Remote Relay Modules REMOTE RELAY MODULE SPECIFICATIONS Operating Power 17 27VAC 50 60 Hz or...

Страница 8: ...the remote sensors or group of sensors exceeds a predetermined caution threshold then the common Caution LED located above the LCD Screen will indicate a caution event Relay outputs can be pre assigne...

Страница 9: ...ntroller can then execute control functions based on each zone By adding optional Remote Relay Modules RRM s distributed control can be achieved in addition to the internal control via the relays insi...

Страница 10: ...y 1 42001 Relay 2 Etc 42039 Relay 40 The following data is available for each SENSOR 40xx0 Enable State Gas ID 0 Disabled 1 99 GasID 40xx1 Status 0 OK 1 Fail 2 Caution 4 Warning 8 Alarm 40xx2 Zone Ass...

Страница 11: ...ect Zone 1 8 511 518 No Sensors Zone 1 8 Multi State 101 199 Alarm State Sensor 1 99 201 299 Zone Assignment Sensor 1 99 301 399 RS 485 Port Sensor 1 99 401 499 GasID Sensor 1 99 Binary 1 40 Relay Sta...

Страница 12: ...es not scan the remote sensors and does not activate any warning or alarm relays An automatic timeout returns the ZGARD CX II to normal operation if no keypad activity is detected for 1 minute while i...

Страница 13: ...each their respective warning level then the sensor numbers will be displayed adjacent to the W descriptor Should the number of sensors in a warning condition exceed the physical space provided then a...

Страница 14: ...of remote sensors and is sequentially updated every 2 seconds Column1 The term ZONE reports the zone numbers Column2 The term SNS reports the number of sensors allocated to the current Zone Column3 Th...

Страница 15: ...9 3 2 1 1 O K 1 9 6 0 P P M C O A L A R M R G 1 0 0 P P M R G 1 0 0 C O 1 Z O N E S N S S T A T U S W 1 2 2 2 1 1 O K A 9 3 3 4 A L A R M 8 1 Section 8 ZGARD CX II Controller LCD Screen Display Featu...

Страница 16: ...ZRM is present for zone 2 1 4 0 P P M C O W A R N R G 1 0 0 P P M C Z O N E S N S S T A T U S W 1 4 W A R N A 2 4 W A R N 4 Sensor 1 60ppm alarm 2 45ppm warning Zone 1 ALARM because one or more sensor...

Страница 17: ...h is the default setting The third line implies the programmer to change the setting There are 3 options for the auto configuration program A U T O C O N F I G N O C H A N G E E N T E R A C C E P T Op...

Страница 18: ...e asked to verify the Warning and Alarm set points Press the menu key to accept and continue A U T O C O N F I G 24 S E N S O R S F O U N D 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 V E R I F Y W A...

Страница 19: ...WARNING SETPOINT menu will appear The second line of the display shows the current sensor to be assigned a warning set point level The sensor range is also shown for reference only The third line show...

Страница 20: ...E 0 1 R E S C A N E N T E R U P D A T E 17 2 As the ZGARD CX II scans for external relay cards it displays all cards that are found E X T E R N A L R E L A Y C A R D S A C T I V E 0 1 F O U N D 0 1 2...

Страница 21: ...hich this WARNING relay is assigned A relay may be assigned to multiple zones 20 1 Press the or key to move through all of the relay numbers 20 2 Press 1 through 8 to add or delete a zone that this WA...

Страница 22: ...ntil the desired mode appears 23 2 Next relay number Press the or key to move through all of the relay assignments R E L A Y O P E R A T I O N R E L A Y 1 I N T E R N A L R E L A Y 1 M O D E N O R M A...

Страница 23: ...L A Y F O R C A L I B R A T I O N S E N S O R 1 P O R T 1 R A N G E 1 0 0 P P M G A S L E V E L 0 P P M G A S C O S E N S O R R E F R E S H 3 S E C 32 Press the MENU key 33 The TIME SET menu will app...

Страница 24: ...0 0 F R A M E 8 N 1 M A C 0 0 1 N X T P R V 0 9 V A L U E E N T E R A C C E P T 36 4 Go to next parameter Press the or key to move through all of the desired parameters Not all parameters are changea...

Страница 25: ...Depending on the controller s warning alarm and delay settings the display status and the relay action of the controller may vary Refer to the installation sections of the associated ZGARD CX II Contr...

Страница 26: ...This page left blank...

Страница 27: ...P Zgard CX II ZGARD RRM Ratings Caution Configuration Labels ZGARD CX II B 0 Gas Monitoring Station Power 17 27VAC 50 60Hz or 24 38VDC 0 3Amp 0 7Amp with strobe AC only Input RS 485 99 ZGARD Sensors m...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Отзывы: