Section 1 

ZGARD CX II Controller  

General Information and Specifications 

 
The  ZGARD  CX  II  Controller  is  an  advanced  microprocessor-based  monitoring  system  designed  to  interface 
with  remote  gas  sensors  and  perform  user  configured  control  functions  for  surveillance,  activate  ventilation 
equipment, personnel alert or alarm indication. The controllers feature audible and visual status indicators with 
relay outputs. The controller will automatically detect the total number and type of the remote sensors, actively 
residing  on  the  RS485  network.  Additional  remote  relay  modules  can  also  be  tagged  on  the  communication 
bus, creating a control and surveillance gas alarm monitoring system.  
 
The  ZGARD  CX  II  Controller  provides  programmable  operating  parameters,  which  are  organized  by  a  menu 
interface with keypad and LCD screen. Standard features include a large LCD Screen, audible-visual indication 
and  relay  contact  outputs.  The  remote  gas  sensors  are  connected  via  RS485  serial  communication  ports 
managed  by  the  ZGARD  CX  II  Controller;  up  to  99  sensors  can  be  employed.  The  ZGARD  CX  II  Controller 
acting  as  the  host  governs  the  digital  RS485  serial  communication  and  automatically  coordinates  the  remote 
devices.  MSA  ZGARD  S  or  GS  sensor-transmitters  are  available  to  detect  a  wide  variety  of  gases  including 
Carbon Monoxide, Carbon Dioxide, Nitrogen Dioxide, Refrigerants and Ammonia.  
 

OPERATING SPECIFICATIONS

 

Remote Sensor Input

 

 

RS485 digital data bus, 2-wire connection plus shield

 

Network Capacity 

99 Remote Gas Sensors 

Power Requirements 

19-27 VAC, 50/60 Hz or 24-38 VDC, at 0.3 Amps 
19-27 VAC, 50/60 Hz at 0.7 Amps (with STROBE OPTION) 
To be powered by a class 2 source 

Operating Temperature 
Storage Temperature 

-20° to 50°C (-4° to 122°F) 
-30° to 60°C (-22° to 140°F) 

User Interface 

Keypad on the front panel of the controller with menu driven operating parameters 

Digital Display Screen  

4 Line x 40 Character backlit LCD Screen displays the operating, alarm and fault diagnostic 
status of the system. The display is split in two display mode sections 

Status Display 

Common LED’s for System OK-Green, Caution- Amber, Warning-Amber and Alarm-Red 
Power-Green, Fault-Red, Communication-Red & Green 

Network Communication 

RS485, 2-wire serial communication for remote gas sensors and auxiliary modules 

Auto-Configuration Feature 

Digitally recognized remote devices (Sensors and Auxiliary Modules). Each device residing 
on the RS485 serial data bus shall be automatically assigned as a Node on the network 

Caution/Warning/Alarm  
Setpoints 

Adjustable from 1 to 99% of operating range for each system sensor type 

Number of Relays 

4 assignable DPDT Relays: Relay1, Relay2, Relay3 & Relay4 

Remote Relay Modules (RRM)  

Up to 8 OPTIONAL RRM’S can be connected to the controller. Each relay module adds 4 
assignable  DPDT  relay  outputs.    These  relays are  freely  assignable  from  within  the  CX  II 
configuration menu 

Relay Contacts Rating 

5 Amps , 250Vac. 
5 Amps, 30Vdc. 

Relay Action 

A Caution, Warning & Alarm relay can be defined as Normally Energized or De-Energized 
and Latching or Non-Latching.  A Fault relay is always normally-energized and non-
latching. 

Relay Time Delays 

Menu selected OFF delays, adjustable from 0 to 600 seconds for Caution, Warning and 
Alarm, effectively common to all active channels 

Event Logging 

Event logging of every status change with time & date stamp. Events are stored in non-
volatile memory and can be viewed on LCD Screen or sent to printer via RS-232 port. Up 
to 20,000 events can be stored.  Most recent events over-write oldest events. 

Serial Interface 

MODBUS interface allows retrieval of system status including individual sensor data 
Optional BACnet module allows for integration into BACnet systems 

Set-up and Calibration 

Pre-configured at factory to default settings and configurable by user  

Audible Alarm 

Audible Alarm Device, 93 dB @ 0.3 meters 

Pushbutton 

Alarm Silence feature 

Enclosure 

Polycarbonate, Water- and corrosion-resistant enclosure 

Dimensions 

7” (117 mm) H x 10” (254 mm) W x 3.75” (95 mm) D 

Weight

   

 

3kg (6 lbs.) 

Certification 

UL / CSA 61010-1-2012    File No. 3118354 

 
 

1.0 

Содержание ZGARD CX II

Страница 1: ...ment avec ses instructions Comme tout appareil complexifi ce produit peut vous donner les r sultats anticip s seulement s il est install usag et que le service d entretien sont effectu s d apr s les i...

Страница 2: ...ufacturers of such components THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AND IS STRICTLY LIMITED TO THE TERMS HEREOF SELLER SPECIFICALLY DISCLAIMS ANY WARRANTY OF...

Страница 3: ...llation and as a routine inspection of the system 5 Use only genuine MSA replacement parts when performing any maintenance procedures provided in this manual Failure to do so may seriously impair inst...

Страница 4: ...ays 8 3 Section 9 Operation Configuration Set Up Menu Auto Configuration 9 0 Auto Configuration continued 9 1 Auto Configuration continued Caution Warning and Alarm setup 9 2 Zone Assignment External...

Страница 5: ...the operating alarm and fault diagnostic status of the system The display is split in two display mode sections Status Display Common LED s for System OK Green Caution Amber Warning Amber and Alarm Re...

Страница 6: ...etermine the capacity designation and number of remote gas sensors and configure the controller according to the required application Also refer to the ZGARD CX II controller Installation Outline draw...

Страница 7: ...1 500 meters away from the controller The ZGARD CX II Controller does NOT provide operating power for the Remote Relay Modules REMOTE RELAY MODULE SPECIFICATIONS Operating Power 17 27VAC 50 60 Hz or...

Страница 8: ...the remote sensors or group of sensors exceeds a predetermined caution threshold then the common Caution LED located above the LCD Screen will indicate a caution event Relay outputs can be pre assigne...

Страница 9: ...ntroller can then execute control functions based on each zone By adding optional Remote Relay Modules RRM s distributed control can be achieved in addition to the internal control via the relays insi...

Страница 10: ...y 1 42001 Relay 2 Etc 42039 Relay 40 The following data is available for each SENSOR 40xx0 Enable State Gas ID 0 Disabled 1 99 GasID 40xx1 Status 0 OK 1 Fail 2 Caution 4 Warning 8 Alarm 40xx2 Zone Ass...

Страница 11: ...ect Zone 1 8 511 518 No Sensors Zone 1 8 Multi State 101 199 Alarm State Sensor 1 99 201 299 Zone Assignment Sensor 1 99 301 399 RS 485 Port Sensor 1 99 401 499 GasID Sensor 1 99 Binary 1 40 Relay Sta...

Страница 12: ...es not scan the remote sensors and does not activate any warning or alarm relays An automatic timeout returns the ZGARD CX II to normal operation if no keypad activity is detected for 1 minute while i...

Страница 13: ...each their respective warning level then the sensor numbers will be displayed adjacent to the W descriptor Should the number of sensors in a warning condition exceed the physical space provided then a...

Страница 14: ...of remote sensors and is sequentially updated every 2 seconds Column1 The term ZONE reports the zone numbers Column2 The term SNS reports the number of sensors allocated to the current Zone Column3 Th...

Страница 15: ...9 3 2 1 1 O K 1 9 6 0 P P M C O A L A R M R G 1 0 0 P P M R G 1 0 0 C O 1 Z O N E S N S S T A T U S W 1 2 2 2 1 1 O K A 9 3 3 4 A L A R M 8 1 Section 8 ZGARD CX II Controller LCD Screen Display Featu...

Страница 16: ...ZRM is present for zone 2 1 4 0 P P M C O W A R N R G 1 0 0 P P M C Z O N E S N S S T A T U S W 1 4 W A R N A 2 4 W A R N 4 Sensor 1 60ppm alarm 2 45ppm warning Zone 1 ALARM because one or more sensor...

Страница 17: ...h is the default setting The third line implies the programmer to change the setting There are 3 options for the auto configuration program A U T O C O N F I G N O C H A N G E E N T E R A C C E P T Op...

Страница 18: ...e asked to verify the Warning and Alarm set points Press the menu key to accept and continue A U T O C O N F I G 24 S E N S O R S F O U N D 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 V E R I F Y W A...

Страница 19: ...WARNING SETPOINT menu will appear The second line of the display shows the current sensor to be assigned a warning set point level The sensor range is also shown for reference only The third line show...

Страница 20: ...E 0 1 R E S C A N E N T E R U P D A T E 17 2 As the ZGARD CX II scans for external relay cards it displays all cards that are found E X T E R N A L R E L A Y C A R D S A C T I V E 0 1 F O U N D 0 1 2...

Страница 21: ...hich this WARNING relay is assigned A relay may be assigned to multiple zones 20 1 Press the or key to move through all of the relay numbers 20 2 Press 1 through 8 to add or delete a zone that this WA...

Страница 22: ...ntil the desired mode appears 23 2 Next relay number Press the or key to move through all of the relay assignments R E L A Y O P E R A T I O N R E L A Y 1 I N T E R N A L R E L A Y 1 M O D E N O R M A...

Страница 23: ...L A Y F O R C A L I B R A T I O N S E N S O R 1 P O R T 1 R A N G E 1 0 0 P P M G A S L E V E L 0 P P M G A S C O S E N S O R R E F R E S H 3 S E C 32 Press the MENU key 33 The TIME SET menu will app...

Страница 24: ...0 0 F R A M E 8 N 1 M A C 0 0 1 N X T P R V 0 9 V A L U E E N T E R A C C E P T 36 4 Go to next parameter Press the or key to move through all of the desired parameters Not all parameters are changea...

Страница 25: ...Depending on the controller s warning alarm and delay settings the display status and the relay action of the controller may vary Refer to the installation sections of the associated ZGARD CX II Contr...

Страница 26: ...This page left blank...

Страница 27: ...P Zgard CX II ZGARD RRM Ratings Caution Configuration Labels ZGARD CX II B 0 Gas Monitoring Station Power 17 27VAC 50 60Hz or 24 38VDC 0 3Amp 0 7Amp with strobe AC only Input RS 485 99 ZGARD Sensors m...

Страница 28: ......

Страница 29: ......

Страница 30: ......

Отзывы: