46
ModCon®75 Touch
•
Press the desired Alarm Level to change.
o
To modify any settings, verify the password lock/unlock graphic is unlocked
(Review instructions on page 38 to unlock password lock/unlock graphic).
NOTE:
o
The decimal point must be entered when typing the Alarm Level; the Decimal is not
fixed; therefore, enter 19.5 as shown in Figure 38.
•
Pressing the Alarm Level to change, a new widow will come up.
o
Type 19.5 and press the OK button
Verify the Alarm Level changes to the new number.
•
Repeat the above for each desired Alarm Level change.
NOTE:
o
The ModCon75 Touch Controller displays to one decimal point.
o
With certain sensors (ClO2, CO2, etc.), alarm set points in the Ultima X3 unit may
be represented to two decimal points. In this instance, the ModCon75 Touch
Controller will round to the nearest single decimal.
Figure 39. Displays all changed alarm
settings prior to uploading to X3 transmitter(s).
•
Write SP’s button:
o
Saves all changes to the ModCon75 Touch Controller and Ultima X3.
o
Sets Controller relays (connections located on back of unit) to activate according to
caution, warning or alarm settings set on the Choose Zone event screen.
o
Provides status messages during the save process.
o
Verifies that all values were saved by displaying Done! When complete.
o
Indicates a problem during settings upload by displaying Error Writing! This could
indicate that a value outside an alarm level range was entered such as a %LEL
greater than 60 for a combustible sensor. The setting value in error will
automatically revert to its previous setting.
NOTE:
o
If user does not press Write SP’s, the changes will not be made. A Combustible
sensor alarm level cannot be set Greater than 60%LEL.
Содержание ModCon 75
Страница 15: ...14 ModCon 75 Touch Figure 5 HMI Panel Mounting...
Страница 34: ...33 ModCon 75 Touch Figure 19 HMI Power Supply Connection 0V V 24VDC Figure 20 I O Power Supply Connection...
Страница 60: ...59 ModCon 75 Touch Dimensions Figure 58 Dimensions Front Figure 59 Dimensions Side...
Страница 61: ...60 ModCon 75 Touch Figure 60 Dimensions Top HMI I O Module CPU Module...
Страница 83: ...82 ModCon 75 Touch Figure B 8 Remote Relay Panel Mounting Figure B 9 Remote Relay Panel Mounted...