The software version and serial number of the unit
is displayed.
•
All display LED characters and all fault and alarm LEDs
are activated.
NOTE: During this test, all alarms and channel displays are
still operating in measure mode.
Performing a Configuration Review:
1.
Press the <ESC/TEST> button for five seconds while in
measure mode.
2.
The user password must now be entered.
•
The horn will alarm and the common alarm and fault LEDs
will energize.
•
The default password is 0000 and is entered by using the
<SCROLL UP> and <SCROLL DOWN> buttons for each
digit of the password.
•
Each digit must be validated by pressing the
<VALID> key.
•
On the final digit, the unit will indicate <GOOD> and
<TEST> for successful entry and <BAD> for an
incorrect entry.
•
Channel 1 displays <n1>, indicating channel 1 is ready for
configuration review.
3.
Use the <SCROLL RIGHT> and the <SCROLL LEFT>
buttons to initiate configuration review of the remaining
channels (n2 through n8).
4.
Press the <ACK/VALID> button to review a specific channel’s
configuration.
•
The display will scroll through the selected channel’s
settings.
NOTE: During this review, all alarms and channel displays
are operating in measure mode.
•
Pressing the <ESC/TEST> button at any time during the
configuration review will return the unit back to the
standard measure mode.
Chapter 3, Start-up and Operation
3-16