![MSA GASGARD 8 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/msa/gasgard-8/gasgard-8_instruction-manual_1846477030.webp)
2.
Use the <SCROLL RIGHT> and the <SCROLL LEFT>
buttons to initiate configuration of the remaining channels
(n2 through n8).
3.
Press the <ACK/VALID> button to configure a specific
channel.
To Access the Channel Inhibit <Inh> Mode:
1.
Select <Inh> and press the <ACK/VALID> button.
2.
Use the <SCROLL UP> or <SCROLL DOWN> buttons to turn
the channel inhibit ON or OFF.
•
Selecting ON turns ON the channel outputs.
•
Selecting OFF turns OFF channel outputs.
NOTE: Setting inhibit to OFF inactivates alarm and relay
outputs while activating the channel fault LED and
displaying <Inh> on the channel display.
•
The choice is confirmed by pressing the <ACK/VALID>
button or rejected by pressing the <ESC/TEST> button.
To Access the Alarm <AL> Mode:
1.
Select <AL> and press the <ACK/VALID> button.
2.
Use the <SCROLL UP> or <SCROLL DOWN> buttons to
configure each of the four alarm levels (A1 through A4).
NOTE: Access will be limited to alarm levels set to ON in the
<FACT> configuration.
•
The choice is confirmed by pressing the <ACK/VALID>
button or rejected by pressing the <ESC/TEST> button.
•
Once confirmed, the alarm level selected can be set ON
or OFF by using the <SCROLL UP> or <SCROLL
DOWN> buttons.
•
Once confirmed, the alarm can be set as Latching (LAt),
Half-Latching (HALF), or Non-latching (nLAT) by using the
<SCROLL UP> or <SCROLL DOWN> buttons.
•
Latching Mode requires the <ACK/VALID> button
be pressed after an alarm condition has passed to
de-activate relays, LEDs and the horn.
•
Half-Latching Mode allows the relays and horn to
de-activate after an alarm condition has passed;
Chapter 3, Start-up and Operation