however, alarm LEDs must be de-activated by
pressing the <ACK/VALID> button.
•
Non-Latching Mode allows for automatic
de-activation of relays, LEDs and the horn after an
alarm condition has passed.
•
The choice is confirmed by pressing the <ACK/VALID>
button or rejected by pressing the <ESC/TEST> button.
To Access the Buzzer <bUZ> Mode:
1.
Select <bUZ> and press the <ACK/VALID> button.
2.
Use the <SCROLL UP> and <SCROLL DOWN> buttons to
turn the Buzzer ON or OFF.
NOTE: This software select is for the entire monitor and not
for each individual channel.
•
The choice is confirmed by pressing the <ACK/VALID>
button or rejected by pressing the <ESC/TEST> button.
To Access the External Fault <EFLt> Mode:
1.
Select <EFLt> and press the <ACK/VALID> button.
2.
Use the <SCROLL UP> and <SCROLL DOWN> buttons to
turn the External Fault ON or OFF.
•
When set to ON, an external device (e.g., a pump or reset
switch) can be connected to the appropriate terminal and
changes the common fault status on a state of change.
•
The choice is confirmed by pressing the <ACK/VALID>
button or rejected by pressing the <ESC/TEST> button.
To Access the Date <dAtE> Mode:
1.
Select <dAtE> and press the <ACK/VALID> button.
2.
In user mode, only the time can be changed.
3.
If the time listed is incorrect, press the <ACK/VALID> button
to correct.
4.
Use the <SCROLL UP> or <SCROLL DOWN> buttons to set
the correct time.
NOTE: Enter the time in the military format and in the same
manner as the password.
Chapter 3, Start-up and Operation
3-14