7.5
Installation Inspection
Prior to system start-up or trouble shooting, the entire system should be visually inspected. The following are guidelines for
that inspection.
7.5.1 Controller Installation
•
Controller installed in conformance to instruction manual recommendations.
•
AC power is correctly grounded.
•
Hot AC and relay connections have safety covers installed.
7.5.2 Cabling Installation
•
All splices are soldered or via terminal block.
•
Cabling is away from sources of electrical noise or RFI where possible.
7.5.3 Sensor Module Installation
•
Module installation in conformance with this manual.
•
Modules accessible for calibration.
•
Wiring terminations clean and correct.
7.5.4 Moisture Traps and Rainshields
•
Conduit seals and drains installed to avoid moisture build up in electronics enclosure. Water accumulation in sensor
module enclosures is a major cause of damage and system failures - take precautions to seal electrical conduits and
provide moisture traps and drains to avoid water damage.
•
Model 5311-02 rain shield is recommended for installation in wet areas.
7.5.5 Standard Voltages
•
Regulated DC voltage to be applied to the sensor module must be between 10 VDC and 30 VDC.
7.6
Inspection and Troubleshooting Guide
The inspection and troubleshooting guide can be used to step through the system startup and to determine the appropriate
corrective action if a fault occurs.
SMC 5100-XX-IT Toxic Gas Detector Module
37
US
7 Service
Содержание 5100-03-IT
Страница 5: ...15 5100 88 IT Dimensions 67 SMC 5100 XX IT Toxic Gas Detector Module 5 US...
Страница 20: ...mA Circuit Types 20 SMC 5100 XX IT Toxic Gas Detector Module 4 Installation US...
Страница 21: ...4 20 mA Circuit Type Connections for 5100 XX IT SMC 5100 XX IT Toxic Gas Detector Module 21 US 4 Installation...
Страница 50: ...12 Modbus Memory Map 50 SMC 5100 XX IT Toxic Gas Detector Module 12 Modbus Memory Map US...
Страница 51: ...13 HART SMC 5100 XX IT Toxic Gas Detector Module 51 US 13 HART...
Страница 52: ...52 SMC 5100 XX IT Toxic Gas Detector Module 13 HART US...
Страница 67: ...15 5100 88 IT Dimensions SMC 5100 XX IT Toxic Gas Detector Module 67 US 15 5100 88 IT Dimensions...
Страница 68: ......