4.5
Module Address Switch
For digital interface applications the module address switch (or Modbus node) must be set per the table below.
Position
Address
Position
Address
1
Sensor 1
9
Sensor 09
2
Sensor 2
A
Sensor 10
3
Sensor 3
B
Sensor 11
4
Sensor 4
C
Sensor 12
5
Sensor 5
D
Sensor 13
6
Sensor 6
E
Sensor 14
7
Sensor 7
F
Sensor 15
8
Sensor 8
0
Software Menu
NOTE: Use selector switch to pick Sentry PSG addresses 1 through 8 only. If using Modbus output sensor
addresses 1-15 are available. Position 0 allows the Modbus Address to be set by software menu, in the range
16-254.
18
SMC 5100-XX-IT Toxic Gas Detector Module
4 Installation