Power Data by Country - United States of America
Notes
1.
The Neutral in a US three phase Delta configuration is NOT
the same as the Neutral in a WYE configuration and is never
used by MRMC rigs.
2.
The Neutral on the supply side is NOT used by MRMC rigs.
Only the three hot wires and the earth are connected from the
rig to the X,Y,Z and E. W is not connected.
3.
The transformer recommended here is 11KVA 208VAC three
phase Delta input to three phase 415 WYE output. The earth
connection must be included. The transformer therefore is
required to transform the three phase voltage and transform
3+E (Delta) to 3+N+E (WYE) as required by the Bolt X on
Track.