Mr. Heater | Gas-Fired Low-Intensity Infrared Heater

Operating Instructions and Owner’s Manual

 

MINIMUM HEIGHT FROM ROOF

 

TO LOWEST DISCHARGE OpENING

      

Roof pitch  

H (Min)

 

Flat       to 6/12  

1.0 Feet

 

Over  6/12 to 8/12 

1.5 Feet

 

Over  8/12 to 10/12 

2.5 Feet

 

Over 10/12 to 12/12  

4.0 Feet

 

Over 12/12 to 16/12  

6.0 Feet

 

Over 16/12 to 20/12  

7.5 Feet

2. All other gas vents shall terminate not less than 2 feet (0.6m) 

above the highest point where they pass through the roof and at 
least 2 feet (0.6m) higher than any portion of a building located 
within 10 feet (3.1m) as shown in the following illustration.

Venting/Ducting

 

For Commercial and Industrial Installations 
Only
General Requirements

Use aluminum or teflon tape suitable for 550°F (3M Company tapes 

#433 or #363) or RTV silicone sealant.

Heater must be vented in accordance with specification ANSI 

Z223.1 

- latest revision

. Partial information relating to this specification is 

provided in this section with regard to size and configurations for 
venting arrangements. For complete information consult  

ANSI 

Z223.1 - latest revision

 and applicable local codes. Use the following 

guidelines to help insure an adequate, safe ventin arrangement.

Vent Pipe

 

 (Single Wall)

Seal joint & 

annular space.

2" Clearance

Boot Flashing

Storm Collar

Vent Pipe 

 

Type B  

(Double Wall)

Vent Cap 
Type B

10ft. or less 

 2ft. min.

c) Horizontal Through the Sidewall

This heater, when horizontally vented, must be installed with the 
approved venting system.

When venting the heater horizontally through a combustible 

outside wall, the same requirements listed previously for Venting 

Through the Roof

 apply except as follows:

1.  When venting the heater to the outside of the building through 

a sidewall, use 3 inch O.D. single-wall metal pipe. This is to 
be constructed of galvanized sheet metal or other approved 
noncombustible, corrosion-resistant material as indicated by state 
and/or local codes.

2.  For horizontal venting, the vent lengths may be as follows:

Minimum Equivalent Length = 5 feet of Pipe

Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent 

length:

a) Subtract 15 feet if the run is horizontal

b) Subtract 10 feet for an approved vent cap.

c) Subtract 10 feet for each elbow beyond 15 feet from the heater.

d) Subtract 15 feet for each elbow within 15 feet of the heater.

NOTE

: To minimize problems associated with 

 

 condensation in long runs, vent pipe can be   

 

 insulated.

3.  The horizontal venting system approved with this heater consists 

of the Side Wall Vent Kit (02840) shown are page 3.

4. Limit the quantity of 90° elbows to two. When vent pipe is in a 

horizontal run, it must be pitched downward ¼ inch per foot 
towards the vent terminal. The heater must be installed level.

5. The horizontal venting system shall not terminate:

a) Less than 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, 
or 1 foot (30cm) above any door, window or gravity air inlet into 
any building. The bottom of the vent terminal shall be located 
at least 7 feet (2.1m) above grade or above snow accumulation 
levels as determined by local codes.

b) Less than 3 feet (0.9m) from a combustion air inlet.

c) Less than 3 feet (0.9m) from any other building opening or any 

gas service regulator.

d) Directly over areas where condensate or vapor could create a 
nuisance or hazard or be harmful to the operation of gas utility 
meters, regulators, relief valves, or other equipment. Building 
materials should be protected from flue gases and condensate.

6. In regions of the country where prevailing winds are consistently 

higher than 40 mph, it may be necessary to terminate the vent 

system above the roof level.

Single-Wall 
Vent Pipe

Wall Thimble

Wall

18"

Vent Cap

Type “B” Vent

Содержание HST45

Страница 1: ...any electrical switch do not use any phone in your building supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved for residential Ga...

Страница 2: ...Echec pour se conformer aux precautions et aux in structions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses d...

Страница 3: ...the transfer of body oils from the hands to the surface of the reflector Vent Kit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7...

Страница 4: ...t energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and reflecto...

Страница 5: ...ectrical Rating 120VAC 60Hz single phase 1 amp Connection 3 pin molded plug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input a...

Страница 6: ...nting requirements for the MHT tube heater Specifies the national standards and applicable codes that apply to the gas electric and venting requirements Specifies the national standards and applicable...

Страница 7: ...above the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible...

Страница 8: ...as required Choose Location for Heater When selecting a suitable mounting location for the MHT tube heater it is important to consider the following 1 The heater must meet the minimum mounting height...

Страница 9: ...ontal venting sections must slope away from the heater at a rate of per foot 5 The total length of vent pipe horizontal and vertical runs combined plus the length of the exterior termination must not...

Страница 10: ...nted through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not...

Страница 11: ...he gaskets The tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagr...

Страница 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Страница 13: ...ustible wall refer to the latest edition of the National Fuel Gas Code or the authority having jurisdiction In regions of the country where prevailing winds are consistently higher than 40 mph it may...

Страница 14: ...is is to be constructed of galvanized sheet metal or other approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may b...

Страница 15: ...ength should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A safety switch in...

Страница 16: ...e area opening shall be provided below the heater for each 1 000 Btu hr of heater input When outside air is used the opening below the heater shall be one square inch of free area for each 4 000 Btu h...

Страница 17: ...hown below To check system pressure a plugged 1 8 NPT tapping is required upstream of the manual gas shut off valve supplied with the heater Before connecting the heater to the supply system verify th...

Страница 18: ...ns and burrs 3 Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and w...

Страница 19: ...will then occur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and f...

Страница 20: ...itch does not operate Igniter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power...

Страница 21: ...nlet pressure requirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as requ...

Страница 22: ...ters on the illustrations are keyed to the associated parts list I B A C J F H G D E ITEM PART NUMBER DESCRIPTION HST 35 HST 45 A 02808 Spark Electrode 1 1 B 02837 Ignition Wire 1 1 05795 Orifice MHT...

Страница 23: ...CHASE REF ITEM DESCRIPTION A F202850 MHT 45NG Burner Box for F208850 F202851 MHT 45LP Burner Box for F202851 B F106250 MHT45 Tube Set Long C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT 45 Reflecto...

Страница 24: ...the claim Also supply us with the purchase date and the name and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There a...

Отзывы: