Mr. Heater HST45 Скачать руководство пользователя страница 12

12

Mr. Heater | Gas-Fired Low-Intensity Infrared Heater

Operating Instructions and Owner’s Manual

 

 

Canadian Installations1 

 

US Installations2

A= 

Clearance above grade, 

12 inches (30 cm)   

12 inches (30 cm)

 

veranda, porch, deck or 

 

 

balcony

B= 

Clearance to window or door 

6 inches (15 cm) for appliances 

<

 

6 inches (15 cm) for appliances 

 

that may be opened 

10,000 Btuh (3 kW), 12 inches (30 

10,000 Btuh (3 kW), 9 inches (23

 

 

cm) for appliances > 10,000 Btuh 

cm) for appliances > 10,000 Btuh

 

 

(3 kW) and 

<

 100,000 Btuh (30 

(3 kW) and 

< 50,000 Btuh (15

 

 

kW), 36 inches (91 cm) for 

kW), 12 inches (30 cm) for

 

 

appliances > 100,000 Btuh (30 kW) 

appliances > 50,000 Btuh (15 kW)

C= 

Clearance to permanently 

 

 

 

*

 

closed window

D= 

Vertical clearance to ventilated 

 

 

 

 

soffit located above the

 

terminal within a horizontal 

 

 

 

 

 

 

 

distance of 2 feet (61 cm) from

 

the center line of the terminal

E= 

Clearance to unventilated soffit 

 

 

 

*

F= 

Clearance to outside corner 

 

 

 

 

G= 

Clearance to inside corner 

 

 

 

*

H= 

Clearance to each side of 

3 feet (91 cm) within a height 15

 

center line extended above 

feet (4.5 m) above the 

 

 

*

 

meter/regulator assembly 

meter/regulator assembly

I= 

Clearance to service regulator 

3 feet (91 cm) 

 

 

 

*

 

vent outlet

J= 

Clearance to nonmechanical air 

6 inches (15 cm) for appliances 

 

6 inches (15 cm) for appliances 

 

supply inlet to building or the 

10,000 Btuh (3 kW), 12 inches (30 

10,000 Btuh (3 kW), 9 inches (23 cm)

 

combustion air inlet to any 

cm) for appliances > 10,000 Btuh (3 

for appliances > 10,000 Btuh (3 kW)

 

other appliance 

kW) and 

100,000 Btuh (30 kW), 

and 

 50,000 Btuh (15 kW), 12

 

 

36 inches (91 cm) for appliances 

inches (30 cm) for appliances >

 

 

> 100,000 Btuh (30 kW) 

50,000 Btuh (15 kW)

K= 

Clearance to a mechanical air 

6 feet (1.83 m) 

 

3 feet (91 cm) above if within 10 feet

 

supply inlet 

 

 

(3 m) horizontally

L= 

Clearance above paved 

7 feet (2.13 m) +   

 

 

*

 

sidewalk or paved driveway

 

located on public property

M= 

Clearance under veranda, 

12 inches (30 cm) ++ 

 

 

*

 

porch deck, or balcony 

 

In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

++ 

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:

 

a) A minimum clearance value determined by testing in accordance with section 2.19.6, or; 

 

b) A reference to the following footnote:

 

    “Clearance in accordance with local installation codes and the requirements of the gas supplier.”

Typical Installation 

The Illustration below shows a typical installation of the MHT tube 
heater. The installation drawing shown has a straight horizontal 
venting arrangement and specifies the minimum space required for 
maintenance, as well as the allowable range of distances between 
the two suspension points. 

Detailed venting arrangements are illustrated in following portions of 

this section.

(*) For minimum mounting height in aircraft hangars and public  

garages.

 

X Dimension

  Model  

Min.  

Max.

  MHT-45  

102"  

114"

Minimum 

Recommended

 

for servicing

24"

15"

Vent terminal

Exterior Wall

Outside wall thickness - 
10" max. 1/2" min.

Burner Box

Reflector

Minimum Mounting 

Height- 7 feet*

6" Min

X

1" Max.

Suspension 

Points

Section 4 VENTING

This appliance is certified under the ANS/CSA Standard for Vented 
Gas-Fired Space Heating Appliances. In accordance with these 
standards all sidewall venting must conform to the supplied diagram 
for Vent Terminal Clearances, which are stated for both U.S. and 
Canadian installations. These clearances should be compared 
to but not less than those specified in the current ANSI Z223.1/
NFPA 54, National Fuel Gas Code, or CSA B149.1, Natural Gas and 
Propane Installation Code. Clearances not covered in the table or 
above listed codes must comply with local installation codes and the 
requirements of your local gas supplier.

Содержание HST45

Страница 1: ...any electrical switch do not use any phone in your building supplier If you cannot reach your gas supplier call the Fire Department Gas Fired Low Intensity Infrared Heaters approved for residential Ga...

Страница 2: ...Echec pour se conformer aux precautions et aux in structions a fourni avec cet appareil de chauffage avoir pour resultat la mort blessure et la perte de propriete ou les dommages physiques serieuses d...

Страница 3: ...the transfer of body oils from the hands to the surface of the reflector Vent Kit F102840 1 2 3 x 2 Pipe 26GA 2 1 36 x 3 B Vent 3 1 Gas Vent Top 3 4 1 Adj Wall Thimble 5 1 Storm Collar 6 1 3 Elbow 7...

Страница 4: ...t energy downward to the space to be heated Heat Exchanger A U shaped tube through which the heated products of combustion pass Rear Movable Hanger Provides support for the heat exchanger and reflecto...

Страница 5: ...ectrical Rating 120VAC 60Hz single phase 1 amp Connection 3 pin molded plug Gas Inlet Connection Connection Male NPT Gas Inlet Pressure The minimum inlet gas supply pressure for the purpose of input a...

Страница 6: ...nting requirements for the MHT tube heater Specifies the national standards and applicable codes that apply to the gas electric and venting requirements Specifies the national standards and applicable...

Страница 7: ...above the floor Minimum required safe distances to combustibles must be maintained from vehicles parked below the heater When installed over hoists the minimum required safe distances to combustible...

Страница 8: ...as required Choose Location for Heater When selecting a suitable mounting location for the MHT tube heater it is important to consider the following 1 The heater must meet the minimum mounting height...

Страница 9: ...ontal venting sections must slope away from the heater at a rate of per foot 5 The total length of vent pipe horizontal and vertical runs combined plus the length of the exterior termination must not...

Страница 10: ...nted through the roof be sure to carefully review the roof option installa tion portion of this section Ensure that the selected mounting site will satisfy the measurement param eters vent length not...

Страница 11: ...he gaskets The tube ends extend through the flanges to help with alignment 3 Using the four long and four short nuts from the bolt kit 02876 secure the tube set to the burner box As shown in the diagr...

Страница 12: ...current CSA B149 1 Natural Gas and Propane Installation Code 2 In accordance with the current ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved d...

Страница 13: ...ustible wall refer to the latest edition of the National Fuel Gas Code or the authority having jurisdiction In regions of the country where prevailing winds are consistently higher than 40 mph it may...

Страница 14: ...is is to be constructed of galvanized sheet metal or other approved noncombustible corrosion resistant material as indicated by state and or local codes 2 For horizontal venting the vent lengths may b...

Страница 15: ...ength should be shortened or insulated g For vent specifications all of the following conditions must be met The maximum equivalent length of vent pipe should be carefully observed A safety switch in...

Страница 16: ...e area opening shall be provided below the heater for each 1 000 Btu hr of heater input When outside air is used the opening below the heater shall be one square inch of free area for each 4 000 Btu h...

Страница 17: ...hown below To check system pressure a plugged 1 8 NPT tapping is required upstream of the manual gas shut off valve supplied with the heater Before connecting the heater to the supply system verify th...

Страница 18: ...ns and burrs 3 Use LP resistant joint compound on all threads 4 Check the pipe and tube connections for leaks before placing heating equipment into service When checking for gas leaks use a soap and w...

Страница 19: ...will then occur 8 Periodic visual check of burner flame while unit is in operation through sight glass in bottom of unit Section 6 MAINTENANCE Pre Season Maintenance Heater area to be kept clear and f...

Страница 20: ...itch does not operate Igniter spark gap incorrect Try This Unplug heater power cord from the electrical outlet wait for a minimum of five seconds Plug heater cord back into outlet Unplug heater power...

Страница 21: ...nlet pressure requirements contact the gas company Check for 24V across valve terminals Check Shutoff On Valve IF NO Check wiring between the ignition module and the valve Repair replace wires as requ...

Страница 22: ...ters on the illustrations are keyed to the associated parts list I B A C J F H G D E ITEM PART NUMBER DESCRIPTION HST 35 HST 45 A 02808 Spark Electrode 1 1 B 02837 Ignition Wire 1 1 05795 Orifice MHT...

Страница 23: ...CHASE REF ITEM DESCRIPTION A F202850 MHT 45NG Burner Box for F208850 F202851 MHT 45LP Burner Box for F202851 B F106250 MHT45 Tube Set Long C 06014 Hanger D 06016 Hanger Clamp E 06008 9 MHT 45 Reflecto...

Страница 24: ...the claim Also supply us with the purchase date and the name and address of the dealer from whom you purchased our product The foregoing is the full extent of the responsibility of the Company There a...

Отзывы: