PAGE 42 — DA7000SSA3 GENERATOR• OPERATION MANUAL — REV. #0 (02/13/19)
7. Verify that the AC voltmeter (Figure 54) on the welder-
generator reads zero volts.
Figure 54. AC Voltmeter (Zero Volts)
8. Next, place the main circuit breaker, CB1 (Figure 55)
in the
ON
position.
Figure 55. Main Circuit Breaker (ON)
9. To restore power, press the
RESET
button on the
GFCI sensing module (Figure 56) and verify that the
red fault LED turns
OFF
and the green power LED
should turn
ON
.
Figure 56. GFCI Sensing Module
(Green LED ON Reset)
MAINTENANCE
10. Verify that the AC voltmeter is registering a voltage
reading as indicated by Figure 57.
Figure 57. AC Voltmeter (120/240V)
NOTICE
It is recommended that the GFCI sensing module be
tested when the generator is initially taken out of the
box. Then, the generator should be tested daily at
startup.
CAUTION
The GFCI module is designed to interrupt power when
a ground fault exists to prevent injuries and shock
hazards.
DO NOT
operate the generator if this test
fails. Consult a qualified electrician for the repair or
replacement of the GFCI module.