DA7000SSA3 GENERATOR• OPERATION MANUAL — REV. #0 (02/13/19) — PAGE 41
TESTING THE GFCI SENSING MODULE
If tripping of the
main
circuit breaker persists after a load is
replaced with a known good one (no short circuit), perform
this test with no load.
1. Start the welder-generator as outlined in the start up
procedure in this manual.
2. Place the main circuit breaker, CB1 (Figure 49) in the
ON
position.
Figure 49. Main Circuit Breaker ON (GFCI Test)
3. On the GFCI sensing module, verify that the green
power LED is ON (Figure 50).
Figure 50. GFCI Sensing Module (Green LED ON)
MAINTENANCE
4. Verify that the AC voltmeter is registering a voltage
reading as shown in Figure 51.
Figure 51. AC Voltmeter (Normal)
5. Next, press the
TEST
button on the GFCI sensing
module (Figure 52) and verify that the
green
POWER
LED turns
OFF
and the
red
FAULT LED turns
ON
.
Figure 52. GFCI Module (Red/Fault LED ON)
6. Also verify that the main circuit breaker (Figure 53)
switch trips to the
OFF
position.
Figure 53. Circuit Breaker OFF (GFCI Test)