ioLogik R2140
Modbus/RTU Address Mappings
B-7
Reference Address Data Type
Description
40027
0x001A 1 word
CH6 AI power-on range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value
40028
0x001B 1 word
CH7 AI power-on range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value
40029
0x001C 1 word
CH0 AI safe range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value
40030
0x001D 1 word
CH1 AI safe range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value
40031
0x001E 1 word
CH2 AI safe range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value
40032
0x001F 1 word
CH3 AI safe range
00: +/-150 mV
01: +/-500 mV
02: +/-5V
03: +/-10V
04: 0-20 mA
05: 4-20 mA
Other: return illegal data value