12
—
Turbo Ring DIP Switch Settings
EDS-P510 series are plug-and-play managed redundant Ethernet switches. The
proprietary Turbo Ring protocol was developed by Moxa to provide better
network reliability and faster recovery time. Moxa Turbo Ring’s recovery time
is less than 300 ms (
Turbo Ring
) or 20 ms (
Turbo Ring V2
) —compared to a
3- to 5-minute recovery time for commercial switches—decreasing the possible
loss caused by network failures in an industrial setting.
There are 4 Hardware DIP Switches for Turbo Ring on the top panel of
EDS-P510 that can help setup the Turbo Ring easily within seconds. If you do
not want to use a hardware DIP switch to setup the Turbo Ring, you can use a
web browser, telnet, or console to disable this function.
NOTE
Please refer to the
Turbo Ring DIP Switch
section and
Using
Communication Redundancy
section in User’s Manual for more
detail information about the settings and usage of
Turbo Ring
and
Turbo Ring V2
.
EDS-P510 Series DIP Switches
2
1
------
MASTER
COUPLER
TURBO
RING
4
3
The default setting for each DIP Switch is OFF. The
following table explains the effect of setting the DIP
Switch to the ON position.
“Turbo Ring” DIP Switch Settings
DIP 1
DIP 2
DIP 3
DIP 4
ON: Enables this
EDS as the Ring
Master.
ON: Enables the
default “Ring
Coupling” ports.
ON: Activates
DIP switches 1,
2, 3 to configure
“Turbo Ring”
settings.
Reserved for
future use.
OFF: This EDS
will not be the
Ring Master.
OFF: Do not use
this EDS as the
ring coupler.
OFF: DIP
switches 1, 2, 3
will be disabled.
“Turbo Ring V2” DIP Switch Settings
DIP 1
DIP 2
DIP 3
DIP 4
ON: Enables the
default “Ring
Coupling
(backup)” port.
ON: Enables this
EDS as the Ring
Master.
ON: Enables the
default “Ring
Coupling” port.
ON: Activates
DIP switches 1,
2, 3 to configure
“Turbo Ring V2”
settings.
OFF: Enables the
default “Ring
Coupling
(primary)” port.
OFF: This EDS
will not be the
Ring Master.
OFF: Do not use
this EDS as a
ring coupler.
OFF: DIP
switches 1, 2, 3
will be disabled.