- 6 -
STEP 3
—Once the screws are fixed
to the wall, insert the four screw
heads through the wide parts of the
keyhole-shaped apertures, and then
slide the EDS-510A downwards, as
indicated in the figure at the right.
Tighten the four screws for more
stability.
ATEX Information
1.
Certificate number DEMKO 08 ATEX 0810937x
2.
Ambient range (-40°C
≤
Tamb
≤
75°C)
3.
Certification string (Ex nA nC IIC T4 Gc)
4.
Standards covered ( EN 60079-0:2012, EN60079-15:2010)
5.
The conditions of safe usage:
•
These products must be mounted in an IP54 enclosure.
•
Install in an area of pollution degree 2 or less.
•
Use a conductor wire of size 0.2 mm
²
or greater.
•
PROVISIONS SHALL BE MADE, EITHER IN EXTERNAL TO THE
APPARATUS, TO PREVENT THE RATED VOLTAGE BEING
EXCEEDED BY THE TRANSIENTS DISTURBANCES OF MORE
THAN 40 %
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with the
Safety Extra-Low Voltages (SELV) in compliance with IEC950/
EN60950/ VDE0805.
ATTENTION
This unit is a built-in type. When the unit is installed in another
piece of equipment, the equipment enclosing the unit must
comply with fire enclosure regulation IEC 60950/EN60950 (or
similar regulation).