6.
Setting of Parameters
6.1.
Basic Parameters
In general, the parameters described subsequently must be set with the very first
commissioning of the unit only. For best comprehensibility, this section describes setup of all
display functions only first. Settings applicable to relay outputs and serial interface are
described separately.
Keep ENTER and SET down simultaneously for 3 seconds to access the basic parameters.
Menu Text
Default
Mode of operation
Single input operation (input A only)
Dual input operation (input A and input B separately)
Sum operation (input A + input B)
Differential operation (input A – input B)
Dividing operation (ratio A : B)
Multiplying operation (product A x B)
Brightness of the display
„100“
„ 100“
100% of maximum brightness
„ 80“
80% of maximum brightness
„ 60“
60% of maximum brightness
„ 40“
60% of maximum brightness
„ 20“
20% of maximum brightness
Update time of the display
„0.300“
Updates the display every x.xxx seconds. Setting range from
0.050 to 5.999 seconds.
Keypad interlock code
Keypad enabled continuously
Keypad locked for any access
Keypad locked, except for access to preselections
Pres 1 und Pres 2
Mode of linearization
No linearization. The corresponding parameters will
not appear in the menu.
Linearization for the numeric range 0 – 99999.
Interpolation points to be set in the positive range
only (negative values will appear as a mirror).
Linearization over the full range
–99999 to +99999