VMX
2
Series Digital Solid State Soft Starter User Manual
88 |
P a g e
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F065
C
om
m
un
ic
a
ti
ons
Communications
0 = Disabled
1 = Enabled (11Bit)
2 = Enabled (10Bit)
1
0
F066
Baud Rate
4.8, 9.6 and 19.2 KB
3 rates
9.6 KB
F067
Modbus Address
1 - 247
1
1
F068
Remote Starter Control
0=Disabled,
1=Enabled combine w/ Start button
2=As option 1, w/o Start button
3=[a. F113= 1 or 5:
Enabled w/ Local/Remote switch
dedicated by Jog button. Jog switch
or button closed is for Remote,
opened for Local.
b. F113 = other value: Enabled.]
Note:
Stop button stops motor in all
the remote control modes.
1
0
F069
Reserved for factory use
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F070
S
y
s
te
m
S
e
tt
ings
Parameter Lock
Customer Password
0 - 999
0 = Disabled
Any Other Numbers = Password
1
0
(displays
encrypted
code)
F071
System Clear / Reset
0 = Disabled
1 = Clear THR and Lockout Timers
2 = Reset to Factory Default
Settings
1
0
F072
Reserved for Factory Use
F073
Frame Rating
10
– 2000
Factory set
1
By Model
(defaults
to 48)
F074
CT Value
10
– 2000
Factory set
5
By Model
(defaults
to 40)
F075
Year
2000 - 2047
1 year
2000
F076
Month
1 - 12
1 Month
1
F077
Day
1 - 31
1 Day
1
F078
Hour
0 - 23
1 Hour
0
F079
Minute
0 - 59
1 Minute
0
F080
Second
0 - 59
1 Second
0
F081
Revision #
-
-
Factory
Setting
F082 -
F084