VMX
2
Series Digital Solid State Soft Starter User Manual
87 |
P a g e
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F048
Lock
outs
,
R
e
s
e
t
a
nd
Int
e
rna
l
P
rot
e
c
ti
on
Coast Down (Back Spin)
Lockout Timer
0 = Disabled, or 1 - 60 minutes
1 minute
0
Disabled
F049
Maximum Starts per Hour
0 = Disabled, or 1 - 10 starts
1
0
Disabled
F050
Minimum Time Between
Starts
0 = Disabled, or 1 - 60 minutes
1 minute
0
Disabled
F051
nCP Trip (No Control
Power)
0, 1 [0=Disabled, 1=Enabled]
1
0
F052
Auto Reset
on Selected Faults
Fault Preferences 1 - 17
See Table 5.6.7:
”Auto-Reset Selected Faults”
1
4,
Phase
Loss only
F053
Auto Reset Attempts
0 = Disabled, or 1-10 attempts
[In 1 minute cycle]
1
0
Disabled
F054
Restart Delay Time Value
Readout (for F028)
0 - 999 Seconds
N/A
Read
Only
F055
Coast Down Timer Value
for F048
1 - 3600 Seconds
F056
Starts Per Hour Timer Value
for F049
1 - 3600 Seconds
F057
Starts Per Hour
For F049
1 - 10 Starts
F058
Time Value Between Starts
for F050
1 - 3600 Seconds
F059
Thermal Capacity to Start
for F005
0 - 100 % Thermal Capacity
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F060
Out
put Re
la
y
s
Aux Relay 1 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
1
F061
Aux Relay 2 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
2
F062
Aux Relay 3 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
16
F063
Aux. Relay Delay Timer
(for Operations 28-31)
0 (Disabled), or 1-999 seconds
1 second
0
No Delay
F064
Reserved for factory use