VMX
2
Series Digital Solid State Soft Starter User Manual
32 |
P a g e
5.5.7 Line Voltage
5.5.8
Current and Ground Fault Protection Features
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F029
Li
ne
V
o
lt
a
ge
Voltage Input
200 - 690 Volt
1
480
1
5.6.7
F030
Voltage Imbalance Trip %
0, 1 - 30% [0=Disabled]
1(%)
0
F031
Voltage Imbalance Trip Delay
1 - 20 seconds
1
10
F032
Over Voltage Trip %
0, 1 - 10% [0=Disabled]
1(%)
0
F033
Over Voltage Trip Delay
1 - 20 seconds
1
10
F034
Under Voltage Trip on Start %
0, 1 - 20% [0=Disabled]
1(%)
0
F035
UV Trip on Start Delay
1 - 180 seconds
1
10
F036
Under Voltage Trip on Run %
0, 1 - 20% [0=Disabled]
1(%)
0
F037
UV Trip Delay during Run
1 - 20 seconds
1
2
F038
Shorted SCR and Trip Delay
0, 1-10 seconds [0=Disabled]
1 second
1 second
F039
Shunt Trip Delay
0, 1-10 seconds [0=Disabled]
1 second
1 second
Table 5.5.7: Line Voltage Function Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F040
P
has
e
C
urre
nt
Current Imbalance Trip
0, 5 - 30%
[0 = Disabled]
1%
0
Disabled
1
5.6.8
F041
Current Imbalance Trip Delay
1 - 20 seconds
1 second
2 seconds
F042
Over Current Trip
0, 100 - 300% of motor FLA
[0 = Disabled]
1%
0
Disabled
F043
Over Current Trip Delay
1 - 20 seconds
1 second
1 second
F044
Under Current Trip
0, 10 - 90% of motor FLA
[0 = Disabled]
1%
0
Disabled
F045
Under Current Trip Delay
1 - 60 seconds
1 second
2 seconds
F046
Ground Fault Trip
0, 5 - 90% of CT ratio from Fn 074
[0 = Disabled]
1%
0
Disabled
F047
Ground Fault Trip Delay
1 - 60 seconds
1 second
2 seconds
Table 5.5.8: Current and Ground Protection Features Group