VMX
2
Series Digital Solid State Soft Starter User Manual
64 |
P a g e
5.6.17 Display & System Settings
F111 = Display Setting
Factory Setting = 10
Range = 1 - 12, 0 (Off)
Sets default display monitor
Value
Display
Definition
1
XXXX. (A) or
XX.XX. (kA)
Ia: Phase A Current (With a dot “.” Shown at bottom right corner
of rightmost digit.)
Shows XX.XX if Iavg>9999 Amp. e.g.12.50 means 12.5 kA.
2
XXXX (A) or
XX.XX (kA)
Ib: Phase B Current
Shows XX.XX if Iavg>9999 Amp.
3
XXXX (A) or
XX.XX (kA)
Ic: Phase C Current
Shows XX.XX if Iavg>9999 Amp.
4
GXXX
Igf: Ground Fault Current
5
UXXX
Uab: Line Voltage AB
6
UXXX
Ubc: Line Voltage BC
7
UXXX
Uca: Line Voltage CA
8
L
XXX (
L
is like superscript) or
L
XXX (
L
is like subscript)
Power Factor (A large L is for Lead and a small L is for lag).
Either of them is shown at leftmost digit)
9
PXXX
KW (w/o decimal point) or MW (w/ decimal point):
Kilo-watt (range: 000 - 999);
Mega-watt (range: 0.00 - 9.99)
10
XXXX (A) or
XX.XX (kA)
Iavg: Average of 3 Phase Currents (It is factory default display);
Shows XX.XX if Iavg>9999 Amp.
11
UXXX
Uavg: Average of 3 Line Voltages
12
HXXX
Thermal Capacity Remaining
F112 = System Settings - Reserved
F113 = Alternate functions for Ramp2/Jog inputs
Factory Setting = 7
Range = 0 - 7
Sets system settings.
Quick Setup of F113:
Data
Dual Ramp Input
Jog Input
0
Dual Ramp
Jog
1
Dual Ramp
Remote / Local
2
Dual Ramp
Ext. Lockout N/O button
3
Dual Ramp
Ext. Lockout N/C button
4
RESET
Jog
5
RESET
Remote / Local
6
RESET
Ext. Lockout N/O button
7
RESET
Ext. Lockout N/C button
Note:
When Jog Input is set to
“Remote/Local”, “Remote” is
communication as set in F068,
and “Local” is normal control via
the terminal strip.