Series Digital Solid State Soft Starter User Manual
35 |
P a g e
5.5.13 Fault History and Run Time
5.5.14
Phase Protection Settings
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F085
Faul
t
H
is
tory
a
nd
R
un
D
a
ta
Fault History #1, Latest Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
N/A
Read
Only
Read
Only
5.6.13.
a
F086
Time Stamp, Fault #1
Based on F078-80
00.0
23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F087
Date Stamp, Fault #1
Based on F076-77
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F088
Fault History #2, Previous
Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
F089
Time Stamp, Fault #2
00.00 - 23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F090
Date Stamp, Fault #2
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F091
Fault History #3, Oldest Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
F092
Time Stamp, Fault #3
00.00 - 23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F093
Date Stamp, Fault #3
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F094
Run Time, Hours
000.0 - 999.9 hours
5.6.13.
b
F095
Run Time,
1000 Hour Overflow
0000 - 9999 thousand hours
F096
Run Cycle Counter
0000 - 9999 times
F097
Run Cycle Counter
10K overflow
0000 - 9999 10 thousand times
Table 5.5.13: Fault History and Run Data Group
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F098
P
has
e
a
n
d
Fre
quenc
y
P
rot
e
c
ti
on
Phase Rotation Trip
0, 1 or 2
0=Disabled, 1=ABC, 2=ACB]
1
0
1
5.6.14
F099
Phase Rotation Trip Delay
1 - 3 seconds
1
1
F100
Phase Loss Trip Delay during
Stop
0 - 20 seconds
[0 = Disabled]
1
1
F101
Phase Loss Trip Delay during
Running
0 - 20 seconds
[0 = Disabled]
1
3
Table 5.5.14: Phase Protection Function Group