VMX-agility Series Quick Start Guide 
MAN-AGY-014. Version 02. 04/10/2019 

 

 

 
 

Mounting 

Fix the unit to a flat, vertical surface using the mounting holes (or slots) on its base-plate. The mechanical outline 
diagrams, shown on Page 4, give the dimensions and mounting hole positions for each model. Ensure that: 

 

The orientation of the unit has the ‘TOP’ 

uppermost. 

 

The location allows adequate front access. 

 

You can view the touchscreen. 

 

Do not install other equipment that generates significant heat close to the soft starter. 

Requirements for an Enclosure 

For a typical industrial environment, an enclosure would provide the following: 

 

A single location for the unit and its protection/isolation switch-gear 

 

The safe termination of cabling and/or busbars 

 

Means to effect proper air flow through the enclosure 

 

Enclosure Ventilation 

When  fitting  VMX-agility

TM

 into a cabinet, ventilation must be provided if the heat  output of the unit is 

greater than the cabinet will dissipate. The heat dissipated can be approximated with the formula: 
Starting 
Watts (agility) = start current(A) x start time(s) x number of starts per hour/1800 
Running 
Watts (agility) = 0.4 x running amps 
Use the following formula to determine the fan requirement. An allowance has been incorporated into the 
formula so that the figure for Q is the air delivery in the fan supplier

s’

 data. 

 

Q = (4 x W

t

 / (T

max

-T

amb

)) 

 

Q = Volume of air (cubic metres per hour-m3/h) 
Wt  =  Heat  produced  by  the  unit  and  all  other  heat  sources  within  the  enclosure  (Watts)  T

max 

=  Maximum 

permissible temperature within the enclosure (40°C for a fully rated agility

™)

 

T

amb

 = Temperature of the air entering the enclosure (°C) [to work in CFM, substitute °F for °C. Q is now in CFM]

 

Altitude Derate 

Altitude  above  sea  level  1000m  (3281ft).  Above  1000m  de  rate  by  1%  of  agility  i.e.  per  100m  (328ft)  to  a 
maximum altitude of 2000m (6562ft). 

Ambient Temperature Derate 

-20°C (-4°F) to 40°C (104°F). Above 40°C de-rate linearly by 2% of agility i.e. per °C to a maximum of 60°C (140°F). 
 

 

Installation

 

 

 
 
 

 

Содержание VMX-agility

Страница 1: ...Innovation in soft start technology VMX agilityTM QUICK START GUIDE MAN AGY 014 Version 0...

Страница 2: ...ics UK deliverables including magnetic optical and or any other soft copy of these deliverables This document may not be reproduced in full or in part without written permission Enquiries about copyri...

Страница 3: ...information contained in this manual is subject to change at any time and without prior notice In no event will responsibility or liability be accepted for direct indirect or consequential damages re...

Страница 4: ...ovided if the heat output of the unit is greater than the cabinet will dissipate Theheat dissipated can be approximated with the formula Starting Watts agility start current A x start time s x number...

Страница 5: ...us injury or damage to equipment Accessories The following accessories have been developed and tested for use with the agility range of soft starts VMX AGY 012 Remote keypad for VMX AGY 101 to VMX AGY...

Страница 6: ...VMX AGY 101 to VMX AGY 113 Weight 1 97kg 3 75lb Fitting 25mm 0 98 25mm 0 98 75mm 2 95 75mm 2 95 25mm 0 98 Installation continued Air Flow inch Note VMX agility may be horizontally mounted with deratio...

Страница 7: ...0 2019 Dimensions VMX AGY 201 to VMX AGY 205 Weight 6 kg 13 22LB VMX AGY 201 to VMX AGY 207 6 3 kg 13 89 VMX AGY 209 Fitting 25mm 0 98 100mm 3 93 100mm 3 93 Installation continued inch 40mm 1 57 40mm...

Страница 8: ...AN AGY 014 Version 02 04 10 2019 Dimensions VMX AGY 301 to VMX AGY 305 Weight 15kg 33 10lb 125mm 4 92 Air Flow Installation continued 60mm 2 36 60mm 2 36 125mm 4 92 25mm 0 98 inch 13 1 332 2 4 60 6 4...

Страница 9: ...be supplied as an option for short circuit protection of the semiconductors These fuses must be fitted externally to the VMX agilityTM chassis to comply with certain standards It is the responsibility...

Страница 10: ...lectrical Connections Mains Circuit Wiring Diagram Electrical Installation continued 3 Phase Electrical Supply Connections L1 L2 L3 RJ45 connector Modbus RTU USB Connector Control Terminals AC Inducti...

Страница 11: ...Gear Provided by customer L N PE Single Phase Operation VMX agilityTM soft starts may be operated with a single phase supply and motor The base rating of the unit is unchanged Electrical Connection E...

Страница 12: ...ed 24Vdc 3 250Vac 2A Cos 0 5 Digital Input 2 D2 Selectable Functions Different functions may be assigned to Digital Input 2 in the I O menu Available assignments are Reset Hold Start Ramp Enable Fire...

Страница 13: ...dc Note 110 230V control supply possible with optional control supply module VMX AGY 021 or VMX AGY 020 for models VMX AGY 101 to VMX AGY 113 only K1 0V K2 2 24V D1 D2 13 0V COM 14 21 22 FU1 24V dc No...

Страница 14: ...rmined by the Motor Current setting and the Trip Class setting Trip class choices are Class 10 Class 20 and Class 30 The VMX agilityTM soft starters are protected using full I 2 T motor overload with...

Страница 15: ...e A flashing centre button indicates that a menu item may be selected or saved Configuration and Parameters Status messages Instantaneous motor current Control scheme Local Control terminal Modbus RTU...

Страница 16: ...Quick Start Guide MAN AGY 014 Version 02 04 10 2019 Operation Local Motor Start Example Navigation Method Auto Application Setup Configuration and Parameters continued Quick Return to Status Screen Ce...

Страница 17: ...High Inertia 40 10 0 30 3 5 60 Fan Low Inertia 30 15 0 10 3 5 30 Grinder 40 10 0 20 3 5 40 Mill 40 10 0 20 3 5 40 Mixer 10 10 0 20 4 25 Moulding M C 10 10 0 10 4 5 25 Press Flywheel 40 10 0 20 3 5 40...

Страница 18: ...pply Number of poles 3 main poles 2 main poles controlled by semiconductor switching element Rated insulation voltage Ui Main circuit See Key to part numbers Control supply circuit 230Vac r m s 1 Rate...

Страница 19: ...frequency dc Rated voltage Uc 24Vdc With VMX AGY 020 VMX AGY 021 module Control Supply Supply input L N Kind of current rated frequency ac 50 60Hz 5Hz Rated voltage Us 110V to 230Vac Rated input curr...

Страница 20: ...applies when the finger guards as supplied are fitted 7 Transient surge suppression shall be installed on the line side of this equipment and shall be rated 600_V phase to phase suitable for overvolt...

Страница 21: ...UL508 Table 6 4 and UL508A Table 15 1 Environmental Specifications Model VMX AGY 101 103 105 107 109 111 113 Frame Size 1 Heat output W 9 12 14 16 20 25 30 Weight kg lb 1 97 4 20 Model VMX AGY 201 203...

Страница 22: ...elay Fuses with a Maximum Rating of ___Z1___ or by a Circuit Breaker with a Maximum Rating of ___Z2___ 2 Correctly selected semiconductor fuses can provide additional protection against damage to the...

Страница 23: ...100 250 300 VMX AGY 303 VMX AGY 305 361 110 200 250 361 125 125 150 300 350 VMX AGY 305 Rating Table Horizontally Mounted Ie kW 1 FLA Hp 2 Trip Class 10 Trip Class 20 Trip Class 30 A 3 230V 400V 500V...

Страница 24: ...toka Spodaj opisana dela smejo izvajati samo elektrostrokovnjaki in elektrotehni no pou ene osebe Nebezpe enstvo ohrozenia ivota elektrick m pr dom Pr ce ktor s ni ie op san sm vykon vat iba elektroo...

Отзывы: