16
VMX-agility Series Quick Start Guide
MAN-AGY-014. Version 01 28/05/2019
Auto Application Setup Parameter Settings
Initial
Volts
Start
Time
Stop
Time
Trip
Class
Current
Limit
Current
Limit Time
Unit
%
s
s
-
*FLC
s
Default
20%
10
0
10
3.5
30
Heavy
40%
10
0
20
4
40
Agitator
30%
10
0
10
3.5
25
Compressor 1
40%
15
0
20
3.5
25
Compressor 2
35%
7
0
10
3.5
25
Conveyor Loaded
10%
10
7
20
5.5
30
Conveyor Unloaded
10%
10
7
10
3.5
30
Crusher
40%
10
0
30
3.5
60
Fan High Inertia
40%
10
0
30
3.5
60
Fan Low Inertia
30%
15
0
10
3.5
30
Grinder
40%
10
0
20
3.5
40
Mill
40%
10
0
20
3.5
40
Mixer
10%
10
0
20
4
25
Moulding M/C
10%
10
0
10
4.5
25
Press Flywheel
40%
10
0
20
3.5
40
Pump 1
10%
10
60
10
3.5
25
Pump 2
10%
10
60
20
3.5
25
PumpJack
40%
10
0
20
3.5
40
SawBand
10%
10
0
10
3.5
25
SawCircular
40%
10
0
20
3.5
40
Screen Vibrating
40%
10
0
20
4.5
40
Shredder
40%
10
0
30
3.5
60
Wood Chipper
40%
10
0
30
3.5
60
Compressor 1 = Centrifugal, Reciprocating, Rotary Screw
Compressor 2 = Rotary Vane, Scroll
Pump 1 = Submersible: Centrifugal, Rotodynamic
Pump 2 = Positive Displacement: Reciprocating, Rotary
Configuration and Parameters (continued)