VMX-agility Series Quick Start Guide
MAN-AGY-014. Version 02. 04/10/2019
24V
COM
0V
13
D1
14
D2
22
21
Control Terminal Connections
Control Terminal Functions
#1 24Vdc Specification: See General Specification (page 19) for VA rating, residual ripple < 100mV,
spikes/switching peaks < 240mV, Turn On/Off response no overshoot of Vout, Overvoltage voltage protection
output voltage must be clamped <30Vdc
#2 The voltage applied to the digital inputs D1 and D2 must not exceed 24Vdc
#3
250Vac, 2A, Cosø =0.5
Digital Input 2 (D2) Selectable Functions
Different functions may be assigned to Digital Input 2 in the I/O menu. Available assignments are:
Reset
Hold Start Ramp
Enable
Fire Mode
In Fire Mode all trips are disabled.
Digital Outputs13,14, 21,22 Selectable Functions
The outputs may be mapped to Fault or Top-of-Ramp, Auto Reset Pending or
Exceeded.
Terminal
Description
Default
Function Selectable
Note
24Vdc
Control Us
-
No
#1
0V
Control Supply -Us
-
No
COM
Digital Inputs Common
-
No
D1
Digital Input 1
-
No
#2
D2
Digital Input 2
-
Yes
#2
13/14
Main Contactor Control (Run Relay)
-
Yes
#3
21/22
Fault Relay
-
Yes
#3
Electrical Installation (continued)