20
VMX-agility Series Quick Start Guide
MAN-AGY-014. Version 01 28/05/2019
Wire Sizes and Torques
Terminal
Models
Wire/Busbar Size
Torque
Metric
Imperial
Nm
Ib-in
Main Terminals
Terminal
VMX-AGY-101 to VMX-AGY-113
2.5 - 70mm
2
12- 2/0AWG
9
80
Cu STR 75
o
C only
VMX-AGY-201 to VMX-AGY-209
4 - 185mm
2
12
–
350MCM
14
124
M10 bolt
VMX-AGY-301 to VMX-AGY-305
2 x 95mm
2
2 x 4/0AWG
28
248
Control Terminals
All models
0.2
–
1.5mm
2
24-16AWG
0.5
4.5
Protective
Earth
1)
M6 screw
VMX-AGY-101
≥ 4
mm
2
≥
12AWG
8
71
Cu only
VMX-AGY-103 to VMX-AGY-111
≥ 6
mm
2
≥
10AWG
VMX-AGY-113 to VMX-AGY-203
≥ 10
mm
2
≥
8AWG
M8 screw
VMX-AGY-205 to VMX-AGY-209
≥ 16
mm
2
≥
6AWG
12
106
M8 Stud
VMX-AGY-301
≥ 25
mm
2
≥
4AWG
VMX-AGY-303 to VMX-AGY-305
≥ 35
mm
2
≥
3AWG
1)
Protective Earth wire size based on bonding conductor requirements of UL508 Table 6.4 and UL508A Table 15.1.
Environmental Specifications
Model (VMX-AGY-)
101
103
105
107
109
111
113
Frame Size
1
Heat output (W)
9
12
14
16
20
25
30
Weight kg [lb]
1.97 [4.20]
Model (VMX-AGY-)
201
203
205
207
209
Frame Size
2
Heat output (W)
37
49
61
74
90
Weight kg [lb]
VMX-AGY-201-VMX-AGY-207 6.00 [13.23] VMX-AGY-209 6.30 [13.89]
Model (VMX-AGY-)
301
303
305
Frame Size
3
Heat output (W)
111
139
166
Weight kg [lb]
15.00 [33.10]
Ambient Operating Temp.
-20°C [-4°F] to 40°C [104°F] ; above 40°C derate linearly by 2% of VMX-agility Ie per
°C to a maximum of 60°C (140°F)
Transportation and Storage
Temperature
-20°C to 70°C [-4°F to 158°F] continuous
Humidity
max 85% non-condensing, not exceeding 50% @ 40°C [104°F]
Maximum Altitude
1,000m [3281ft]; above 1000m derate by 1% of VMX-agility Ie per 100m (328ft) to
a maximum altitude of 2,000m (6562ft)
Environmental Rating
Main Circuit: IP00 (IP20 with optional finger guards);
Control Circuit: IP20; No corrosive gases permitted
Technical Information/Specification