5 Adjustments
5.1 Time Adjustment Procedures
Time settings for "Jog Time" and "Brake Time" are adjusted by use of dip switches on the front mounted Operator
Interface Module. Time settings are in seconds (set in binary code). Each switch denotes a binary digit from 1 - 7
positions, totalling 127 seconds maximum when all are switched to the "On" position.
Operator Interface Module
5.2 Jog Time Setting
Factory Setting: 7 seconds
The jog time is adjustable from 0-127 seconds and is made using the 7 position dip switch SW2, labeled "Jog
Time". Set the switches according to the jog time required. Setting all the switches to the "Off" position (Jog
Time = 0) will disable this function.
Example:
Setting dip switch positions 1, 2, and 3 to “ON” = 1+2+4
= 7 seconds total jog time.
CAUTION!
Damage to the motor, equipment, brake and/or electrical circuit may occur if this adjustment is not
correct. Setting this switch to less than the factory setting may involve risk to the equipment and affect
normal operations. Setting the jog time too long may result in equipment operating without the benefit of
the DC injection brake. The jog time should typically be set to equal the time it takes the motor to
accelerate the load on start (across- the-line) plus approximately two seconds.
On
1 2 3 4 5 6 7
Switch Positions
Jog Time
1 2 4 8 16 32 64
Time (sec.)