background image

 

Motortronics

 

 

 

 

 

                  

                                                     Page 13

 

 

 

 

2.1.3 

“Braking” 

 

The ABC Series  will enter the braking mode when the motor is given a stop command after being "Armed" (see 

"JOG / ARMED" above). To prevent damaging current spikes, a factory programmed delay allows the existing 

motor magnetic field to decay before DC is applied (see section 5.1). During the "BRAKING" mode, a set of N.C. 

interlock contacts change state and disable the motor starter control circuit during the braking cycle (see section 

4.2.2).  

 

The ABC Series begins injecting a regulated DC braking current and simultaneously digitally times, controls the 

Interlock  Relay  and  monitors  the  Zero  Speed  Sense  Circuit.  Braking  will  continue  until  the  first one  of three 

events occurs: 1) the Zero Speed Sense circuit determines the motor has stopped, 2) the "Brake Time" expires, 

or 3) the unit receives a "Brake Disable" signal input. When braking is complete, the ABC Series  releases the 

Interlock Relay and is ready for another cycle.

 

2.1.4 

Brake OFF 

 

This LED illuminates whenever the ABC  Series  is not actively braking (either because the motor is on or the 

previous braking cycle has been completed). The ABC Series provides a built-in, closed-loop sensing circuit that 

accurately determines when the motor has stopped based on the subtle signals received from the unused motor 

winding. If the Zero Speed Sensing circuit determines that the motor has come to a stop before the Brake Time 

has expired, it will override the brake time setting and shut the ABC Series  off. The "BRAKE OFF" LED will then 

illuminate.  NOTE:  Since  the  Brake  Time  may  expire  prior  to  the  Zero  Speed  override  coming  into  play,  this 

circuit should not be used as a true Zero Speed indicator. 

 

WARNING! 

The ABC Series  DC Injection Brake  requires AC power  for  braking.  Power  loss before  or  during braking 

will result in  the  loss of braking ability, which can be hazardous to  personnel and/or equipment. If braking 

to  a  stop  is  critical  regardless  of  the  availability  of  electrical  power,  mechanical  braking  should  be 

provided as a backup system. The ABC Series brake offers a Mechanical Brake  Release  Relay  specifically 

for  this  purpose. 

 

 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание ABC-100

Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 2: ...3 1 Fault History 16 3 2 Fault Code Table 16 3 3 Event Records 16 4 Wiring 17 4 1 Introduction 17 4 2 Line and Load Connections 17 4 3 Control Connections 20 5 Adjustements 23 5 1 Time Adjustment Proc...

Страница 3: ...uit them Motortronics reserves the right to change specifications of this product and or the contents of this manual without notice As a result supplemental data sheets and or drawings may be associat...

Страница 4: ...the amount of current allowed to flow The DC injection level can be adjusted using the Brake Current Potentiometer on the operator interface module This modulates the applied voltage based upon an RMS...

Страница 5: ...ng the Extra Duty rating instead 1 3 2 Extra Duty Sizing For heavier machine loads such as large chippers punch presses and other flywheel based machines selecting an ABC Series brake based on 200 250...

Страница 6: ...e normal wear and tear to the brake pads or shoes On loads such as vibrating feeders screens or separators damage from mechanical harmonics that occur during coast down can be eliminated by using an A...

Страница 7: ...4 9 ABC 550 550 250 125 200 150 500 300 600 350 5 10 ABC 800 800 350 200 350 200 700 450 900 500 5 10 ABC 1000 1000 400 250 400 300 900 500 1000 600 5 10 NOTES 1 Never exceed the Full Load Amp rating...

Страница 8: ...Motortronics Page 7 N4 12 Outline ABC 50 100 E N4 12 Outline ABC 200 E Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 9: ...Motortronics Page 8 N4 12 Outline ABC 300 400 E N4 12 Outline ABC 550 800 E Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 10: ...Motortronics Page 9 Panels Outline ABC 50 100 Panels Outline ABC 200 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 11: ...Motortronics Page 10 Panels Outline ABC 300 400 Panels Outline ABC 550 800 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 12: ...Motortronics Page 11 Panels Outline ABC 1000 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com...

Страница 13: ...ch indicates the starter status see section 4 3 1 The ABC Series can be programmed to wait a period of time before going into the Armed condition using the Jog feature This feature allows for user set...

Страница 14: ...he ABC Series is not actively braking either because the motor is on or the previous braking cycle has been completed The ABC Series provides a built in closed loop sensing circuit that accurately det...

Страница 15: ...tate NOTE The ABC Series Mechanical Brake Release Relay will set the mechanical brake if the ABC Series brake unit is disabled during the braking mode 2 2 2 Wiring Error The ABC Series unit will recog...

Страница 16: ...as follows see section 4 3 4 OPERATION RELAY STATUS Power On No Change de energized Jog Armed Energizes follows motor starter coil Braking Remains energized Braking Time Completed Zero Speed Override...

Страница 17: ...m metallic particles conductive dust and corrosive gas Free from excessive vibration below 0 5G Open panel units must be mounted in the appropriate type of en closure Enclosure size and type must be s...

Страница 18: ...ied Unit can be source of fatal electrical shocks To avoid shock hazard disconnect main power before working on the unit Warning labels must be attached to terminals enclosure and control panel to mee...

Страница 19: ...ker No greater than 250 No greater than 400 No allowable fuses required 200 1000 Amps Class RK5 Fuse Class J Fuse No greater than 250 No greater than 400 Circuit breaker No greater than 250 WARNING Ma...

Страница 20: ...ent so 20 wire or higher can be used Fuse protection ad equate for the field wiring used must be provided per code NOTE If the ABC Series brake is being used with 2 speed Wye Delta or Reduced Voltage...

Страница 21: ...nical Brake Relay WARNING The motor starter must never be operated manually when the brake unit is connected Blown fuses and or damage to the unit may result 4 3 1 Starter Monitor Input Provides a bra...

Страница 22: ...released i e the contact is opened Once the ABC Series has resumed operation it will evaluate the status of the motor and re enter the JOG mode if conditions are correct Circuit voltage potential 15VD...

Страница 23: ...may occur and the warranty on the unit may be voided 4 3 4 Mechanical Brake Release Relay The ABC Series brake unit can work in conjunction with a mechanical brake by interfacing with the motor and al...

Страница 24: ...ting all the switches to the Off position Jog Time 0 will disable this function Example Setting dip switch positions 1 2 and 3 to ON 1 2 4 7 seconds total jog time CAUTION Damage to the motor equipmen...

Страница 25: ...clamp on ammeter should be used to check the current supplied to the motor while braking Place the meter on one of the ABC Series input power lines Start the motor by energizing the motor starter cont...

Страница 26: ...some reason you need to disable the Zero Speed Sensing remove this jumper The ABC Series will then continue braking for the entire Brake Time setting even if the motor has already come to a complete s...

Страница 27: ...ny one of its input leads with the true RMS AC clamp on ammeter Adjust the brake current if necessary If the brake times out before the motor stops increase the value of the brake time switch or incre...

Страница 28: ...nd status annunciation Braking current is adjustable via true RMS regulated control using phase angle firing of SCRs Operator Adjustments Brake Time and Jog Time 7 position binary dip switch Brake Cur...

Страница 29: ...sabled this circuit controls the mechanical brake normally as if it is the only brake in the system Aux Contact Ratings 5 Amps 250 VAC max LED Status Indicators Large LEDs braking green Fault Red Smal...

Страница 30: ...ntrols have different operating characteristics from those of electromechanical equipment Because of these differences and the wide variety of applications for solid state controls each application de...

Отзывы: