Motortronics
Page 19
4.2.2
Load Power Connections
Connect the motor leads to the output terminals T1 and T2 provided on the unit. The unit will operate on either a
Wye or a Delta connected motor. An additional control wire must be run from motor lead T3 of the starter to the
voltage sensing circuit of the ABC Series. The terminal for this is marked "T3". This terminal carries very little
current so #20 wire (or higher) can be used. Fuse protection ad- equate for the field wiring used must be
provided per code.
NOTE: If the ABC Series brake is being used with 2-speed, Wye- Delta or Reduced Voltage starter, consult
factory for additional load connection information.
CAUTION!
Power Factor Correction Capacitors should NOT be connected to the load side of the motor starter when
used with an ABC Series brake. PFC Capacitors should only be connected to the line side and must
include a separate isolation contactor.