![Motortech VariSCR Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/motortech/variscr/variscr_operating-manual_1839339082.webp)
8 Settings via the MICT
82
Rev. 06/2020
The following information is displayed in the individual areas of the window:
Catalyst Intake
/
Catalyst Outlet
For the two NO
X
sensors at the intake and outlet of the catalytic converter, you will receive the
following information:
–
NO
X
The green status display indicates that the NO
X
measurement of the sensor is working
correctly. In addition, the status of the NO
X
measurement and the actual measured value are
displayed.
–
Oxygen
The oxygen content is also determined by the NO
X
sensor. The green status display indicates
that the measurement of the oxygen content is working correctly. In addition, the status of
the oxygen measurement and the actual measured value are displayed.
–
Power
The green status display indicates that the supply voltage is within the permissible range. In
addition, the status of the supply voltage is displayed.
–
Heater
The green status display indicates that the heating of the NO
X
sensor is active and is
working without errors. In addition, the status and operating mode of the heater are
displayed.
–
Online
The green status indicator indicates that the respective NO
X
sensor is communicating with
the emission controller.
Temperature
The temperature module consists of two temperature sensors for intake and outlet.
–
Catalyst Intake / Catalyst Outlet
The current measured value and the status of the respective sensor are indicated for each of
the two temperature sensors.
–
ECU
The temperature of the temperature module and the status of the entire module will be
indicated.
–
Online
The green status indicator indicates that the temperature module is communicating with the
emission controller.