8 Settings via the MICT
68
Rev. 06/2020
–
Continuous Self Test
The continuous self test is performed permanently during operation of the emission
controller.
Refer to the section
Pump Self Test
You have the following options:
–
Overall Timeout
Enter the total time for the initial self-test, after which the pressure and speed tests must be
completed successfully at the latest. If the time is not observed, the self-test is aborted and
the emission controller goes into the error mode.
–
Pressure
Activate the checkbox to monitor the pump pressure.
–
Timeout
If the pressure is not within the specified minimum and maximum values within the
specified time, the self-test is aborted and the emission controller goes into error mode.
–
Min. Pressure
/
Max. Pressure
Enter the limits for the pump pressure.
–
Speed
Activate the checkbox to monitor the pump speed.
–
Timeout
If the pump speed is not within the specified minimum and maximum values within the
specified time, the self-test is aborted and the emission controller goes into error mode.
–
Min. Speed/Max. Speed
Enter the limits for the pump speed.