8 Settings via the MICT
Rev. 06/2020
55
Device -> Manual pump adjustment
The speed entered in the dialog window is set and held at the start of the test until a timeout
occurs or the pressure range configured for the initial pump self test is reached (see
Exhaust
Control – SCR – Pump Self Test
on page 67).
You have the following options:
–
Parameters
Enter the speed and timeout for the test. When the dialog window is opened, the values
correspond to the settings of the initial pump self test.
–
Control
–
Start
Click the button to start the test.
–
Set
Click the button to transfer the changed parameters to the emission controller.
–
Stop
Click the button to stop a running test.
The status displays have the following meaning:
–
Running
The test has been started and is running without errors.
–
Speed Timeout
When the status display lights up, the speed did not match the value specified in the
Speed
field for longer than the time specified in the field
Timeout
.
–
Pressure Timeout
When the status display lights up, the pressure range specified in the initial self test has not
been reached within the
Timeout
(see
Exhaust Control – SCR – Pump Self Test
on page 67).
–
Success
The required pump pressure was reached within the time specified under
Timeout
.